Analysis of Lightning Grounding Values Using Variations in Frequency, Distance Ratio, and Measurement Methods

The aim of this research was to determine the frequency, distance ratio, and measurement method on the grounding measurement results for the lightning protection system. The methods used in this study were the 3-poles, 4-poles, and impedance impulse methods. Referring to the fall of potential (FOP) theory, the measurements were conducted by placing the current probe at a variation of the distance ratio of <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$56 \%, 59 \%, 62 \%, 65 \%$</tex>, and 68 %. The frequency ranges were from 55 Hz to 15.4 kHz, except for the impedance impulse method. The result that the impedance increased from 1.87Ω to 7.36Ω as the frequency increased from 55 Hz to 15.4 kHz. The impedance also increased from 1.66Ω to 2.78Ω as the distance ratio increased from 56 % to 68 %. The graph indicated that the 4-poles method generally produced the lower impedance compared to the 3 -poles method. Thus, the performance evaluation of lightning protection system should consider the characteristics of grounding values which could vary depending on the given variables.

Authors

Institutions

Publication Details

Published
2025-06-17
DOI
https://doi.org/10.1109/apl65034.2025.11108783
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of Lightning Grounding Values Using Variations in Frequency, Distance Ratio, and Measurement Methods

Tumiran, Yusuf Susilo Wijoyo, Mochammad Wahyudi, M. Isnaeni Bambang Setyonegoro et al.
Lightning and Electromagnetic Phenomena
article

Analysis of Lightning Grounding Values Using Variations in Frequency, Distance Ratio, and Measurement Methods

Tumiran, Yusuf Susilo Wijoyo, Mochammad Wahyudi, M. Isnaeni Bambang Setyonegoro, Muhammad Alfian Mukti Sampurno
article en

Abstract

The aim of this research was to determine the frequency, distance ratio, and measurement method on the grounding measurement results for the lightning protection system. The methods used in this study were the 3-poles, 4-poles, and impedance impulse methods. Referring to the fall of potential (FOP) theory, the measurements were conducted by placing the current probe at a variation of the distance ratio of <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$56 \%, 59 \%, 62 \%, 65 \%$</tex>, and 68 %. The frequency ranges were from 55 Hz to 15.4 kHz, except for the impedance impulse method. The result that the impedance increased from 1.87Ω to 7.36Ω as the frequency increased from 55 Hz to 15.4 kHz. The impedance also increased from 1.66Ω to 2.78Ω as the distance ratio increased from 56 % to 68 %. The graph indicated that the 4-poles method generally produced the lower impedance compared to the 3 -poles method. Thus, the performance evaluation of lightning protection system should consider the characteristics of grounding values which could vary depending on the given variables.

Universitas Gadjah Mada (ID)
Climate action
Openalex Percentile: Top 85%
Lightning and Electromagnetic Phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.