Protection Principle of DC Line Based on Fault Component of Line Mode Voltage with Current-Limiting Reactor
High-resistance faults on the DC lines of multi-terminal VSC-HVDC grids lead to insufficient protection reliability, and the introduction of current-limiting strategies alters the system’s intrinsic fault characteristics, degrading protection performance. To address these issues, we propose a DC-line protection scheme that is immune to converter control strategies and highly tolerant to fault resistance. First, based on the grid topology, post-fault current paths are analyzed, and the fault characteristics produced solely by the fault-induced voltage source are identified. A sequential overlapping derivative transformation is then employed to magnify the discrepancy between internal and external faults, forming the core of the fault-identification criterion; the zero-mode component is used for pole selection. Finally, a four-terminal VSC-HVDC model is built in PSCAD/EMTDC version 4.6.2 for validation. Simulation results show that, after applying the current-limiting strategy, the characteristic quantity changes only marginally, and the proposed protection can reliably withstand fault resistances of up to 700 Ω.
Authors
- Zhihui Dai (ORCID: https://orcid.org/0000-0002-0155-4019)
- Xianzhi Wang (ORCID: https://orcid.org/0000-0001-9582-3445)
- Mingyu Luo (ORCID: https://orcid.org/0009-0008-9148-6363)
- Weimin Zhang (ORCID: https://orcid.org/0000-0003-1133-5001)
- Tiecheng Li (ORCID: https://orcid.org/0000-0003-4455-7057)
- Shiyan Liu (ORCID: https://orcid.org/0009-0009-6116-1506)
- Qingquan Liu
Institutions
- Electric Power Research Institute (US)
- North China Electric Power University (CN)
Publication Details
- Journal
- Energies
- Published
- 2025-08-11
- DOI
- https://doi.org/10.3390/en18164271
- Citations
- 2
- Primary Topic
- HVDC Systems and Fault Protection
- Type
- article
- Field-Weighted Citation Impact
- 1.46