The progressive replacement of conventional power plants equipped with Synchronous Generators (SGs) by Inverter-based Resources (IBRs), like Photovoltaic (PV), Wind Turbine (WT) and Battery Energy Storage Systems (BESSs) power plants, introduces challenges related to the availability of frequency and voltage regulation resources. To address the primary frequency regulation (PFR) needs, Transmission System Operators (TSOs) have introduced dedicated grid code attachments allowing IBRs to contribute to PFR. Moreover, also the converters connected to High Voltage Direct Current (HVDC) links may participate in PFR. This study, conducted in collaboration with Terna, the Italian TSO, assesses the impact of HVDC converters and IBRs on the PFR capability of the Italian transmission network, with a focus on a potentially critical market zone in the 2030 year. The analysis considers two scenarios: <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$i$</tex>) the participation of SGs, IBRs, and two HVDC links (HVDC2 and HVDC3) in PFR, and ii) an extended scenario including the additional contribution of HVDC-1. The analyzed contingency considers possible failures of conventional or wind turbine Generating Units (Gus), single or coupled AC lines or single HVDC modules. In both scenarios, frequency containment actions successfully limited the steady-state frequency deviation within <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\pm 500[\text{mHz}]$</tex>, with HVDC-1 further improving frequency containment capacity.

Authors

Institutions

Publication Details

Published
2025-05-29
DOI
https://doi.org/10.1109/aeithvdc66044.2025.11079478
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Assessment of the Impact of HVDC Links on Frequency Containment Capacity in a Portion of the Italian Transmission Network

Andrea Bonfiglio, Cosimo Pisani, Giovanni Rinzo, Marco Invernizzi et al.
HVDC Systems and Fault Protection
article

Assessment of the Impact of HVDC Links on Frequency Containment Capacity in a Portion of the Italian Transmission Network

Andrea Bonfiglio, Cosimo Pisani, Giovanni Rinzo, Marco Invernizzi, Giorgio Maria Giannuzzi, Matteo Fresia, Luca Orrù, Giuseppe Lisciandrello, Renato Procopio
article en

Abstract

The progressive replacement of conventional power plants equipped with Synchronous Generators (SGs) by Inverter-based Resources (IBRs), like Photovoltaic (PV), Wind Turbine (WT) and Battery Energy Storage Systems (BESSs) power plants, introduces challenges related to the availability of frequency and voltage regulation resources. To address the primary frequency regulation (PFR) needs, Transmission System Operators (TSOs) have introduced dedicated grid code attachments allowing IBRs to contribute to PFR. Moreover, also the converters connected to High Voltage Direct Current (HVDC) links may participate in PFR. This study, conducted in collaboration with Terna, the Italian TSO, assesses the impact of HVDC converters and IBRs on the PFR capability of the Italian transmission network, with a focus on a potentially critical market zone in the 2030 year. The analysis considers two scenarios: <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$i$</tex>) the participation of SGs, IBRs, and two HVDC links (HVDC2 and HVDC3) in PFR, and ii) an extended scenario including the additional contribution of HVDC-1. The analyzed contingency considers possible failures of conventional or wind turbine Generating Units (Gus), single or coupled AC lines or single HVDC modules. In both scenarios, frequency containment actions successfully limited the steady-state frequency deviation within <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\pm 500[\text{mHz}]$</tex>, with HVDC-1 further improving frequency containment capacity.

Terna (Italy) (IT), University of Genoa (IT)
Openalex Percentile: Top 82%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.