Interruption Phenomenon Analysis and Optimization Research on the Conventional HVDC Converter Valve in Asynchronous Interconnected Power System

This paper provides an in-depth analysis of the issue of direct current interruption in the conventional HVDC converter valve in asynchronous interconnected power system. Through trigger channel verification and optical intensity testing, it was found that the interruption on-site was caused by a weak intensity of the received light, which prevented normal triggering and was tripped by the action of the break over diode (BOD) after the voltage rise. After extensive experimental analysis, a solution was proposed to reasonably increase the input light intensity margin of the thyristor and reduce the current limiting resistance of the valve control system. The proposed solution was successfully implemented on-site, effectively resolving the problem of converter valve interruption and ensuring the safe and reliable operation of the asynchronous section between the Yunnan Power Grid and the Southern Power Grid's main network.

Authors

Institutions

Publication Details

Published
2025-05-23
DOI
https://doi.org/10.1109/ieecsc64206.2025.11100018
Primary Topic
High-Voltage Power Transmission Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Interruption Phenomenon Analysis and Optimization Research on the Conventional HVDC Converter Valve in Asynchronous Interconnected Power System

Shufei Li, Yang Jie-min, Jianxiang Huang, Chenguo Yao et al.
High-Voltage Power Transmission Systems
article

Interruption Phenomenon Analysis and Optimization Research on the Conventional HVDC Converter Valve in Asynchronous Interconnected Power System

Shufei Li, Yang Jie-min, Jianxiang Huang, Chenguo Yao, Fukun Peng, Yukun Zhu
article en

Abstract

This paper provides an in-depth analysis of the issue of direct current interruption in the conventional HVDC converter valve in asynchronous interconnected power system. Through trigger channel verification and optical intensity testing, it was found that the interruption on-site was caused by a weak intensity of the received light, which prevented normal triggering and was tripped by the action of the break over diode (BOD) after the voltage rise. After extensive experimental analysis, a solution was proposed to reasonably increase the input light intensity margin of the thyristor and reduce the current limiting resistance of the valve control system. The proposed solution was successfully implemented on-site, effectively resolving the problem of converter valve interruption and ensuring the safe and reliable operation of the asynchronous section between the Yunnan Power Grid and the Southern Power Grid's main network.

Southern University of Science and Technology (CN), China Southern Power Grid (China) (CN)
Affordable and clean energy
Openalex Percentile: Top 82%
High-Voltage Power Transmission Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.