Influence of Electrical-Thermal Aging to the Bar-to-bar Discharge on the End-winding of HV Motors

The space left between adjacent coils on the end-winding can become inadequate during the operation of high voltage (HV) motors due to mechanical vibration or other factors, which can lead to bar-to-bar discharge in the small air gap between two adjacent coils and gradually develop into phase-to-phase or phase-to-ground failures. Additionally, the inadequate spacing can also result in poor heat dissipation, causing excessive temperature rise in the winding and further accelerating the insulation failure process. To better understand the development of bar-to-bar discharge, an accelerated aging experiment was conducted on two stator coils under well-controlled thermal and electrical stresses. The partial discharge (PD) was collected, and the characteristics of phase resolved partial discharge (PRPD) patterns were analyzed along with periodic visual inspection of the insulation surface. It was observed that bar-to-bar discharge always gives rise to constant amplitude during both half cycles of the voltage. Furthermore, the PD distribution changes from “strip-like” shape to “ rabbit-like ” and “ turtle-like ” shape as aging progresses. The PD inception phase shifts forward, approaching the zero crossings of the positive and negative half-cycles, while PD parameters show an increasing trend with aging. Additionally, corona discharge and surface discharge appear and gradually become the dominant discharge types. The research of this paper is devoted to provide a reference for PD monitoring and fault diagnosis of HV motors.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Dielectrics and Electrical Insulation
Published
2025-01-01
DOI
https://doi.org/10.1109/tdei.2025.3590314
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Influence of Electrical-Thermal Aging to the Bar-to-bar Discharge on the End-winding of HV Motors

Lingyan Lin, Bangfa Peng, Ke-Ang Fu, Ailiang Kang et al.
IEEE Transactions on Dielectrics and Electrical Insulation
High voltage insulation and dielectric phenomena
article

Influence of Electrical-Thermal Aging to the Bar-to-bar Discharge on the End-winding of HV Motors

Lingyan Lin, Bangfa Peng, Ke-Ang Fu, Ailiang Kang, Shijie Zhao, Zhanqing Chen, Li Lu, Wei Li, Libing Zhang
article en

Abstract

The space left between adjacent coils on the end-winding can become inadequate during the operation of high voltage (HV) motors due to mechanical vibration or other factors, which can lead to bar-to-bar discharge in the small air gap between two adjacent coils and gradually develop into phase-to-phase or phase-to-ground failures. Additionally, the inadequate spacing can also result in poor heat dissipation, causing excessive temperature rise in the winding and further accelerating the insulation failure process. To better understand the development of bar-to-bar discharge, an accelerated aging experiment was conducted on two stator coils under well-controlled thermal and electrical stresses. The partial discharge (PD) was collected, and the characteristics of phase resolved partial discharge (PRPD) patterns were analyzed along with periodic visual inspection of the insulation surface. It was observed that bar-to-bar discharge always gives rise to constant amplitude during both half cycles of the voltage. Furthermore, the PD distribution changes from “strip-like” shape to “ rabbit-like ” and “ turtle-like ” shape as aging progresses. The PD inception phase shifts forward, approaching the zero crossings of the positive and negative half-cycles, while PD parameters show an increasing trend with aging. Additionally, corona discharge and surface discharge appear and gradually become the dominant discharge types. The research of this paper is devoted to provide a reference for PD monitoring and fault diagnosis of HV motors.

IEEE Transactions on Dielectrics and Electrical Insulation
Taiyuan University of Technology (CN)
Affordable and clean energy
Openalex Percentile: Top 86%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.