Advancing in Data Centers Thermal Management: Experimental Assessment of Two-Phase Liquid Cooling Technology

Abstract The rapid expansion of online platforms and web-based AI has driven a surge in computational power demand and data center growth, necessitating advanced cooling solutions to manage increasing power densities and energy consumption. This study evaluates the effectiveness of a two-phase direct-to-chip liquid cooling system in high-density rack environments. A key focus is the deployment of a 160 kW refrigerant-to-liquid (R2L) coolant distribution unit (CDU), integrated with row and rack manifolds and server cooling loops. To emulate real-world thermal loads, thermal testing vehicles (TTVs) equipped with 2.5 kW heaters covering 2500 mm2 are used to replicate server loads of up to 10 kW. The study details the system's design, commissioning, and extensive hydraulic and thermal testing, emphasizing pressure drops across supply manifolds, cooling loops, and return manifolds. Each cooling loop (CL) incorporates four cold plates (CPs) to optimize heat dissipation. Experimental data from TTV heating demonstrate the efficiency of two-phase cooling in transferring heat to chilled water using R134a refrigerant. At a volumetric flowrate of 0.48 LPM/kW, a Tcase as low as 56.4 °C was achieved, highlighting the system's capability to enhance thermal management for high-power-density chips. These findings validate two-phase cooling as a viable, energy-efficient solution for future data centers, addressing rising computational demands while promoting sustainable thermal regulation strategies.

Authors

Institutions

Publication Details

Journal
Journal of Electronic Packaging
Published
2025-08-04
DOI
https://doi.org/10.1115/1.4069320
Citations
1
Primary Topic
Heat Transfer and Boiling Studies
Type
article
Field-Weighted Citation Impact
0.71
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Advancing in Data Centers Thermal Management: Experimental Assessment of Two-Phase Liquid Cooling Technology

Ahmad R. Gharaibeh, Yaman Manaserh, Russ Tipton, Ali Heydari et al.
1 citations
Journal of Electronic Packaging
Heat Transfer and Boiling Studies
0.71
article

Advancing in Data Centers Thermal Management: Experimental Assessment of Two-Phase Liquid Cooling Technology

Ahmad R. Gharaibeh, Yaman Manaserh, Russ Tipton, Ali Heydari, Omar Al-Zu’bi, Jeremy Rodriguez, Bahgat Sammakia, Mehdi Mehrabi‐Kermani
article en
1 citations

Abstract

Abstract The rapid expansion of online platforms and web-based AI has driven a surge in computational power demand and data center growth, necessitating advanced cooling solutions to manage increasing power densities and energy consumption. This study evaluates the effectiveness of a two-phase direct-to-chip liquid cooling system in high-density rack environments. A key focus is the deployment of a 160 kW refrigerant-to-liquid (R2L) coolant distribution unit (CDU), integrated with row and rack manifolds and server cooling loops. To emulate real-world thermal loads, thermal testing vehicles (TTVs) equipped with 2.5 kW heaters covering 2500 mm2 are used to replicate server loads of up to 10 kW. The study details the system's design, commissioning, and extensive hydraulic and thermal testing, emphasizing pressure drops across supply manifolds, cooling loops, and return manifolds. Each cooling loop (CL) incorporates four cold plates (CPs) to optimize heat dissipation. Experimental data from TTV heating demonstrate the efficiency of two-phase cooling in transferring heat to chilled water using R134a refrigerant. At a volumetric flowrate of 0.48 LPM/kW, a Tcase as low as 56.4 °C was achieved, highlighting the system's capability to enhance thermal management for high-power-density chips. These findings validate two-phase cooling as a viable, energy-efficient solution for future data centers, addressing rising computational demands while promoting sustainable thermal regulation strategies.

Journal of Electronic PackagingVol. 147(4)
Binghamton University (US), OhioHealth (US), Nvidia (United States) (US), Villanova University (US)
Openalex Percentile: Top 29%
Heat Transfer and Boiling Studies
0.71
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.