Method of Determination of Voltage Dip Source Location in Relation to the Border of Balance Responsibility

The uncertainty of voltage dips source location on the border of balance responsibility complicates the timely response of maintenance personnel to faults in the electrical network and also leads to frequent legal disputes between electricity consumers and suppliers. The determination of the fault direction—towards the consumer or the electricity supplier—is carried out by analyzing the negative-sequence voltage on the power line and the negative-sequence current flowing through that line, followed by comparing their relative phase angles. It is important to note that the angular characteristics of voltage dips within an internal network (e.g., within a facility) may significantly differ from those in external networks due to the heterogeneity of networks with different nominal voltage levels. This can affect the angular characteristics and lead to substantial errors. Research also shows that determining torque for the conventional negative-sequence directional element has several limitations: the negative-sequence voltage is inversely proportional to the source power; the fault impedance reduces the level of the negative-sequence current; and the values of the traditional directional torque directly depend on the magnitude of the negative-sequence voltage and current, which limits the ability to accurately determine the fault direction. This work presents the method for identifying the location of a voltage dip relative to the boundary of balance responsibility in a three-phase electrical network by developing a directional element based on the total negative-sequence impedance. In this approach, the total negative-sequence impedance is always negative for forward faults and always positive for reverse faults. The effectiveness of this method for fault direction detection was verified through simulation of a type B voltage dip. The results of the simulation demonstrated acceptable accuracy.

Authors

Publication Details

Journal
Visnyk of Vinnytsia Politechnical Institute
Published
2025-01-01
DOI
https://doi.org/10.31649/1997-9266-2025-180-3-72-78
Primary Topic
Advancements in Materials Engineering
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Method of Determination of Voltage Dip Source Location in Relation to the Border of Balance Responsibility

A.V. Voloshko, Ye.V. Kozlovskyi
Visnyk of Vinnytsia Politechnical Institute
Advancements in Materials Engineering
article

Method of Determination of Voltage Dip Source Location in Relation to the Border of Balance Responsibility

A.V. Voloshko, Ye.V. Kozlovskyi
article en

Abstract

The uncertainty of voltage dips source location on the border of balance responsibility complicates the timely response of maintenance personnel to faults in the electrical network and also leads to frequent legal disputes between electricity consumers and suppliers. The determination of the fault direction—towards the consumer or the electricity supplier—is carried out by analyzing the negative-sequence voltage on the power line and the negative-sequence current flowing through that line, followed by comparing their relative phase angles. It is important to note that the angular characteristics of voltage dips within an internal network (e.g., within a facility) may significantly differ from those in external networks due to the heterogeneity of networks with different nominal voltage levels. This can affect the angular characteristics and lead to substantial errors. Research also shows that determining torque for the conventional negative-sequence directional element has several limitations: the negative-sequence voltage is inversely proportional to the source power; the fault impedance reduces the level of the negative-sequence current; and the values of the traditional directional torque directly depend on the magnitude of the negative-sequence voltage and current, which limits the ability to accurately determine the fault direction. This work presents the method for identifying the location of a voltage dip relative to the boundary of balance responsibility in a three-phase electrical network by developing a directional element based on the total negative-sequence impedance. In this approach, the total negative-sequence impedance is always negative for forward faults and always positive for reverse faults. The effectiveness of this method for fault direction detection was verified through simulation of a type B voltage dip. The results of the simulation demonstrated acceptable accuracy.

Visnyk of Vinnytsia Politechnical InstituteVol. 180(3)
Climate action
Openalex Percentile: Top 81%
Advancements in Materials Engineering
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.