A Single-Ended Protection Scheme for Flexible HVdc Transmission Lines Based on the Fréchet Distance of the Rate of Change of Fault Voltage Traveling Waves

Flexible DC transmission technology is a technical solution for the large-scale integration of renewable energy. To ensure the stable operation of transmission systems, the rapid and selective protection of transmission lines is crucial. However, the existing traveling wave (TW) protection methods have several main problems, such as insufficient tolerance to fault resistance at the remote ends. To address this problem, a protection scheme based on the overall curve characteristics of TWs is proposed. Specifically, a mathematical analysis is conducted on the initial line-mode TW curves, focusing on the differences between the rate-of-change characteristics exhibited by the initial TW under internal and external faults. On the basis of the analyzed mathematical expression, the reference curves of the rate-of-change of traveling waves (ROCOTW) under internal and external faults are subsequently established. The Fréchet distance (FD) is used to quantify the similarity between the reference and the measured curves of the ROCOTW. If the FD between the measured curve and the internal fault reference curve is less than the FD between the measured curve and the external fault reference curve, the simulated fault is determined to be an internal fault. Otherwise, it is determined to be an external fault. Finally, the results show that the proposed scheme can tolerate a fault resistance of <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\,600{\Omega }$ </tex-math></inline-formula> and 35 dB of noise under different grid topologies and a current-limiting reactor (CLR) of 70 mH. This scheme can quickly and accurately distinguish between internal and external faults.

Authors

Institutions

Publication Details

Journal
IEEE Access
Published
2025-01-01
DOI
https://doi.org/10.1109/access.2025.3590150
Citations
1
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.73

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A Single-Ended Protection Scheme for Flexible HVdc Transmission Lines Based on the Fréchet Distance of the Rate of Change of Fault Voltage Traveling Waves

Yilin Zhong, Faxi Peng, Hui Qin, Tao Liu et al.
1 citations
IEEE Access
HVDC Systems and Fault Protection
0.73
article

A Single-Ended Protection Scheme for Flexible HVdc Transmission Lines Based on the Fréchet Distance of the Rate of Change of Fault Voltage Traveling Waves

Yilin Zhong, Faxi Peng, Hui Qin, Tao Liu, Zhen Pan, Runbin Cao
article en
1 citations

Abstract

Flexible DC transmission technology is a technical solution for the large-scale integration of renewable energy. To ensure the stable operation of transmission systems, the rapid and selective protection of transmission lines is crucial. However, the existing traveling wave (TW) protection methods have several main problems, such as insufficient tolerance to fault resistance at the remote ends. To address this problem, a protection scheme based on the overall curve characteristics of TWs is proposed. Specifically, a mathematical analysis is conducted on the initial line-mode TW curves, focusing on the differences between the rate-of-change characteristics exhibited by the initial TW under internal and external faults. On the basis of the analyzed mathematical expression, the reference curves of the rate-of-change of traveling waves (ROCOTW) under internal and external faults are subsequently established. The Fréchet distance (FD) is used to quantify the similarity between the reference and the measured curves of the ROCOTW. If the FD between the measured curve and the internal fault reference curve is less than the FD between the measured curve and the external fault reference curve, the simulated fault is determined to be an internal fault. Otherwise, it is determined to be an external fault. Finally, the results show that the proposed scheme can tolerate a fault resistance of <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\,600{\Omega }$ </tex-math></inline-formula> and 35 dB of noise under different grid topologies and a current-limiting reactor (CLR) of 70 mH. This scheme can quickly and accurately distinguish between internal and external faults.

IEEE AccessVol. 13
China Southern Power Grid (China) (CN), Power Grid Corporation (India) (IN)
Science and Technology Project of State Grid
Openalex Percentile: Top 25%
HVDC Systems and Fault Protection
0.73
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.