Evaluation of Line Side Prospective Transient Recovery and Determination of Current Zero Crossing for Short Line Fault Interruption

The line side prospective transient recovery voltage (TRV) for circuit breakers should be measured by using a switching device with low stray elements and minimized or ideally no effects on the test circuit. A common method is the capacitor current injection circuit with a diode as a switching element described in IEC 62271‐100 annex E.3.3. This paper discusses the diode effects (current zero crossing, voltage drop, stray capacitance) on the determination of the line side TRV. Furthermore, the influence of stray elements from the current measuring sensors such as CTs and shunts on the current zero crossing was investigated. Other procedures to determine the prospective TRV for short line faults are the reverse current injection method and the current step response method. These methods will be introduced in this paper. © 2025 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.

Authors

Institutions

Publication Details

Journal
IEEJ Transactions on Electrical and Electronic Engineering
Published
2025-07-26
DOI
https://doi.org/10.1002/tee.70105
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluation of Line Side Prospective Transient Recovery and Determination of Current Zero Crossing for Short Line Fault Interruption

Tadashi Koshizuka, Md. Abul Kalam Azad
IEEJ Transactions on Electrical and Electronic Engineering
Power Systems Fault Detection
article

Evaluation of Line Side Prospective Transient Recovery and Determination of Current Zero Crossing for Short Line Fault Interruption

Tadashi Koshizuka, Md. Abul Kalam Azad
article en

Abstract

The line side prospective transient recovery voltage (TRV) for circuit breakers should be measured by using a switching device with low stray elements and minimized or ideally no effects on the test circuit. A common method is the capacitor current injection circuit with a diode as a switching element described in IEC 62271‐100 annex E.3.3. This paper discusses the diode effects (current zero crossing, voltage drop, stray capacitance) on the determination of the line side TRV. Furthermore, the influence of stray elements from the current measuring sensors such as CTs and shunts on the current zero crossing was investigated. Other procedures to determine the prospective TRV for short line faults are the reverse current injection method and the current step response method. These methods will be introduced in this paper. © 2025 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.

IEEJ Transactions on Electrical and Electronic EngineeringVol. 21(2)
Tokyo Denki University (JP), Hitachi (Japan) (JP)
Openalex Percentile: Top 79%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.