Current harmonic emission of string inverters based on cable length on a large grid-connected PV plant

The integration of solar photovoltaic systems into distribution networks has grown significantly, bringing benefits but also power quality challenges, such as harmonic distortion. While harmonic emissions from PV inverters have been widely studied, the impact of cable length on harmonic behaviour in large-scale grid-connected PV plants remains underexplored. This work analyses the harmonic emissions of three photovoltaic string inverters in a 35 MW PV plant with varying cable lengths. Key findings reveal that even harmonics (excluding H2) decrease with longer cables, acting as a low-pass filter, while odd harmonics show no clear trend, suggesting additional influencing factors such as inverter switching characteristics. Notably, H2 exhibits an inverse relationship, increasing with cable length. THD I is inversely related to power levels, with THD I below 2% under stable irradiance. Distinct emission patterns are observed at different power levels, with H5 and H7 showing strong power dependence. These results highlight the importance of cable length and power conditions in mitigating harmonic distortions, addressing a critical research gap and offering insights for renewable energy integration. • H5, H7, H11, and H13 are the main current harmonics emitted by the PV plant. • Even harmonics decrease with cable length, except H2, which increases with distance. • Longer cable lengths reduce phase imbalance in harmonic distortion. • H5 and H7 show strong correlation with inverter output power levels. • High-frequency harmonic correlation decreases as cable length increases.

Authors

Institutions

Publication Details

Journal
International Journal of Electrical Power & Energy Systems
Published
2025-07-26
DOI
https://doi.org/10.1016/j.ijepes.2025.110909
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Current harmonic emission of string inverters based on cable length on a large grid-connected PV plant

Estefanía Artigao, Emilio Gómez‐Lázaro, Sergio Martín‐Martínez, A. Carretero-Hernández
International Journal of Electrical Power & Energy Systems
Microgrid Control and Optimization
article

Current harmonic emission of string inverters based on cable length on a large grid-connected PV plant

Estefanía Artigao, Emilio Gómez‐Lázaro, Sergio Martín‐Martínez, A. Carretero-Hernández
article en

Abstract

The integration of solar photovoltaic systems into distribution networks has grown significantly, bringing benefits but also power quality challenges, such as harmonic distortion. While harmonic emissions from PV inverters have been widely studied, the impact of cable length on harmonic behaviour in large-scale grid-connected PV plants remains underexplored. This work analyses the harmonic emissions of three photovoltaic string inverters in a 35 MW PV plant with varying cable lengths. Key findings reveal that even harmonics (excluding H2) decrease with longer cables, acting as a low-pass filter, while odd harmonics show no clear trend, suggesting additional influencing factors such as inverter switching characteristics. Notably, H2 exhibits an inverse relationship, increasing with cable length. THD I is inversely related to power levels, with THD I below 2% under stable irradiance. Distinct emission patterns are observed at different power levels, with H5 and H7 showing strong power dependence. These results highlight the importance of cable length and power conditions in mitigating harmonic distortions, addressing a critical research gap and offering insights for renewable energy integration. • H5, H7, H11, and H13 are the main current harmonics emitted by the PV plant. • Even harmonics decrease with cable length, except H2, which increases with distance. • Longer cable lengths reduce phase imbalance in harmonic distortion. • H5 and H7 show strong correlation with inverter output power levels. • High-frequency harmonic correlation decreases as cable length increases.

International Journal of Electrical Power & Energy SystemsVol. 170
University of Castilla-La Mancha (ES)
Affordable and clean energy
Openalex Percentile: Top 79%
Microgrid Control and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Current harmonic emission of string inverters based on cable length on a large grid-connected PV plant — Estefanía Artigao, Emilio Gómez‐Lázaro, et al. · International Journal of Electrical Power & Energy Systems (2025) | TGRS Research Map | TGRS