Evaluasi dan Mitigasi Distorsi Harmonisa Transformator 1250 kVA Beban Motor Pompa Air

As a fundamental part of modern life, electricity must be both reliable and efficient—qualities that can be affected by issues like voltage unbalance and harmonic distortion. This study investigates power quality in a 1250 kVA transformer that supplies continuous power to water pump motors at PDAM Wendit, which operate 24 hours a day. Data were collected using the Power Logic PM5100, while a passive filter design was developed and tested through simulations in Matlab/Simulink.The results show a Voltage Unbalance Factor (VUF) of 0,32%, which falls within the acceptable range according to NEMA standards. However, the Total Harmonic Distortion of Voltage (THDV) was found to be between 8% and 9,2%, exceeding the 8% limit recommended by IEEE 519-2014. The average power factor measured was 0,9. To address the excessive harmonic distortion, a single-tuned passive filter was designed targeting the dominant third-order harmonics. Simulations revealed that the filter successfully lowered the THDV to below 6% and reduced current by 1,5% to 3,4%. These findings highlight the importance of harmonic mitigation not only in meeting regulatory standards but also in improving energy efficiency, reducing power losses, and ensuring longer operational life for critical equipment like water pump motors.

Authors

Institutions

Publication Details

Journal
ELPOSYS Jurnal Sistem Kelistrikan
Published
2025-06-30
DOI
https://doi.org/10.33795/elposys.v12i2.7330
Primary Topic
Engineering and Technology Innovations
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluasi dan Mitigasi Distorsi Harmonisa Transformator 1250 kVA Beban Motor Pompa Air

Dhimas Dhesah Kharisma, Anang Dasa Novfowan, Mochammad Mieftah
ELPOSYS Jurnal Sistem Kelistrikan
Engineering and Technology Innovations
article

Evaluasi dan Mitigasi Distorsi Harmonisa Transformator 1250 kVA Beban Motor Pompa Air

Dhimas Dhesah Kharisma, Anang Dasa Novfowan, Mochammad Mieftah
article en

Abstract

As a fundamental part of modern life, electricity must be both reliable and efficient—qualities that can be affected by issues like voltage unbalance and harmonic distortion. This study investigates power quality in a 1250 kVA transformer that supplies continuous power to water pump motors at PDAM Wendit, which operate 24 hours a day. Data were collected using the Power Logic PM5100, while a passive filter design was developed and tested through simulations in Matlab/Simulink.The results show a Voltage Unbalance Factor (VUF) of 0,32%, which falls within the acceptable range according to NEMA standards. However, the Total Harmonic Distortion of Voltage (THDV) was found to be between 8% and 9,2%, exceeding the 8% limit recommended by IEEE 519-2014. The average power factor measured was 0,9. To address the excessive harmonic distortion, a single-tuned passive filter was designed targeting the dominant third-order harmonics. Simulations revealed that the filter successfully lowered the THDV to below 6% and reduced current by 1,5% to 3,4%. These findings highlight the importance of harmonic mitigation not only in meeting regulatory standards but also in improving energy efficiency, reducing power losses, and ensuring longer operational life for critical equipment like water pump motors.

ELPOSYS Jurnal Sistem KelistrikanVol. 12(2)
State University of Malang (ID)
Openalex Percentile: Top 84%
Engineering and Technology Innovations
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.