Analysis of the Influence of the Degree of Mixing of Insulating Oil with Synthetic Ester on the Dielectric Loss Factor of Impregnated Electrotechnical Papers in a Wide Frequency Spectrum

The article presents the results of laboratory tests of cellulose insulation samples TERTRANS® N 125 and cellulose-aramid NOMEX®910 impregnated with a mixture of synthetic ester MIDEL®7131 and mineral oil NYTRO® 10X, in the form of dispersion characteristics of capacitance, dielectric loss factor and complex permittivity in the range of measuring voltage frequency from 10 mHz to 5 MHz. The aim of the tests was to analyze the effect of the degree of mixing of dielectric liquids on the above characteristics. It was shown that this effect is significant for the operation of power transformers, in which a decision was made to replace mineral oil with a modern, biodegradable dielectric liquid, which is synthetic ester MIDEL®7131. The final result of the research was the determination of frequency windows in which the analysis of changes in the composition of dielectric liquids is most visible. The presented test results may be helpful in future extended diagnostics of power transformer insulation, which will be subjected to the dielectric liquid replacement procedure.

Authors

Institutions

Publication Details

Published
2025-05-18
DOI
https://doi.org/10.1109/icdl63868.2025.11068254
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of the Influence of the Degree of Mixing of Insulating Oil with Synthetic Ester on the Dielectric Loss Factor of Impregnated Electrotechnical Papers in a Wide Frequency Spectrum

S. Wolny
Power Transformer Diagnostics and Insulation
article

Analysis of the Influence of the Degree of Mixing of Insulating Oil with Synthetic Ester on the Dielectric Loss Factor of Impregnated Electrotechnical Papers in a Wide Frequency Spectrum

S. Wolny
article en

Abstract

The article presents the results of laboratory tests of cellulose insulation samples TERTRANS® N 125 and cellulose-aramid NOMEX®910 impregnated with a mixture of synthetic ester MIDEL®7131 and mineral oil NYTRO® 10X, in the form of dispersion characteristics of capacitance, dielectric loss factor and complex permittivity in the range of measuring voltage frequency from 10 mHz to 5 MHz. The aim of the tests was to analyze the effect of the degree of mixing of dielectric liquids on the above characteristics. It was shown that this effect is significant for the operation of power transformers, in which a decision was made to replace mineral oil with a modern, biodegradable dielectric liquid, which is synthetic ester MIDEL®7131. The final result of the research was the determination of frequency windows in which the analysis of changes in the composition of dielectric liquids is most visible. The presented test results may be helpful in future extended diagnostics of power transformer insulation, which will be subjected to the dielectric liquid replacement procedure.

Opole University of Technology (PL)
Openalex Percentile: Top 85%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Analysis of the Influence of the Degree of Mixing of Insulating Oil with Synthetic Ester on the Dielectric Loss Factor of Impregnated Electrotechnical Papers in a Wide Frequency Spectrum — S. Wolny · (2025) | TGRS Research Map | TGRS