Virtual impedance (VI) is widely used in grid-forming (GFM) converters to improve adaptability to stiff grid. However, there are various forms and positions of VI, and the impact of different VI configurations on the impedance characteristics and stability of GFM converters remains underexplored. To address these issues, this paper investigates different types of VI implementations, establishes impedance models for the GFM converter with various VI types, and performs stability analysis. It is revealed that whether the converter output current or the grid current is used as the VI signal, both have identical impedance reshaping effects. Furthermore, compared to placing VI at the modulation stage, adding VI to the voltage loop reference yields the most significant improvement in interaction stability. Finally, simulation results validate the accuracy of the impedance model and the correctness of the theoretical analysis.

Authors

Institutions

Publication Details

Published
2025-06-22
DOI
https://doi.org/10.1109/pedg62294.2025.11060201
Primary Topic
High-Voltage Power Transmission Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

The Impact of Virtual Impedance on System Stability in Grid-Forming Converters with Cascaded Control Structure

Pengjiang Ge, Hao Luo, Zhi Yuan, Kun Wang et al.
High-Voltage Power Transmission Systems
article

The Impact of Virtual Impedance on System Stability in Grid-Forming Converters with Cascaded Control Structure

Pengjiang Ge, Hao Luo, Zhi Yuan, Kun Wang, Jing Ge, Dan Dong
article en

Abstract

Virtual impedance (VI) is widely used in grid-forming (GFM) converters to improve adaptability to stiff grid. However, there are various forms and positions of VI, and the impact of different VI configurations on the impedance characteristics and stability of GFM converters remains underexplored. To address these issues, this paper investigates different types of VI implementations, establishes impedance models for the GFM converter with various VI types, and performs stability analysis. It is revealed that whether the converter output current or the grid current is used as the VI signal, both have identical impedance reshaping effects. Furthermore, compared to placing VI at the modulation stage, adding VI to the voltage loop reference yields the most significant improvement in interaction stability. Finally, simulation results validate the accuracy of the impedance model and the correctness of the theoretical analysis.

State Grid Corporation of China (China) (CN), China Electric Equipment Group (China) (CN)
Affordable and clean energy
Openalex Percentile: Top 85%
High-Voltage Power Transmission Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.