Performance optimization of an office building with a dynamic façade system

A calibrated building energy simulation model assessed a dynamic façade system (including shading and natural ventilation) in an office, achieving a mean absolute error of 2.1% for heating and cooling. Several operational strategies were evaluated, optimizing shading via solar irradiance setpoint. Integrating natural ventilation yielded a 14.9% energy reduction compared to a no-ventilation scenario. Sensitivity analysis showed minimal total energy changes with different occupancy densities and natural ventilation rates, yet occupancy density strongly affected the heating-to-cooling ratio. Broadening heating and cooling setpoints further reduced energy use, highlighting the system’s significant potential for efficient office design.

Authors

Institutions

Publication Details

Journal
International Journal of Ventilation
Published
2025-06-30
DOI
https://doi.org/10.1080/14733315.2025.2524918
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Performance optimization of an office building with a dynamic façade system

Magdalena Hajdukiewicz, Pieter-Jan Hoes, Marcel Loomans, Zhijian Wang et al.
International Journal of Ventilation
Building Energy and Comfort Optimization
article

Performance optimization of an office building with a dynamic façade system

Magdalena Hajdukiewicz, Pieter-Jan Hoes, Marcel Loomans, Zhijian Wang, Hailin Zheng
article en

Abstract

A calibrated building energy simulation model assessed a dynamic façade system (including shading and natural ventilation) in an office, achieving a mean absolute error of 2.1% for heating and cooling. Several operational strategies were evaluated, optimizing shading via solar irradiance setpoint. Integrating natural ventilation yielded a 14.9% energy reduction compared to a no-ventilation scenario. Sensitivity analysis showed minimal total energy changes with different occupancy densities and natural ventilation rates, yet occupancy density strongly affected the heating-to-cooling ratio. Broadening heating and cooling setpoints further reduced energy use, highlighting the system’s significant potential for efficient office design.

International Journal of VentilationVol. 25(1)
Ollscoil na Gaillimhe – University of Galway (IE), Eindhoven University of Technology (NL)
European Commission, Technische Universiteit Eindhoven
Sustainable cities and communities
Openalex Percentile: Top 84%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.