Research on the Mechanism of Extra Fast Transient Overvoltage of Gas Insulated Switchgear Equipment Based on the Tripping Event of 500kV Huangping Plant Station

In response to the bus and main transformer tripping accident triggered by the isolation switch not closing in place at 500kV Huangping plant station, this paper combines onsite inspection, returning to the plant for disassembly and simulation analysis to systematically reveal the fault mechanism. It is found that the disconnecting switch motor blocking module coil breakage leads to the dynamic and static contacts not closing in place, which triggers the gap discharge and extra fast transient overvoltage (VFTO), and finally causes the thermal collapse of the circuit breaker voltage equalizing capacitor. The cumulative thermal effect of VFTO on the voltage-averaging capacitor is verified by electromagnetic transient simulation, and improvement measures for equipment manufacturing, condition monitoring and emergency response are proposed, which provide a theoretical basis for the operation and maintenance and design optimization of Gas Insulated Switchgear(GIS) equipment.

Authors

Institutions

Publication Details

Published
2025-04-25
DOI
https://doi.org/10.1109/nesp65198.2025.11040655
Citations
2
Primary Topic
Geoscience and Mining Technology
Type
article
Field-Weighted Citation Impact
2.61
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on the Mechanism of Extra Fast Transient Overvoltage of Gas Insulated Switchgear Equipment Based on the Tripping Event of 500kV Huangping Plant Station

Pengfeng Qiu, Xin Wang, Dong Zhou, Zhaoyu Peng et al.
2 citations
Geoscience and Mining Technology
2.61
article

Research on the Mechanism of Extra Fast Transient Overvoltage of Gas Insulated Switchgear Equipment Based on the Tripping Event of 500kV Huangping Plant Station

Pengfeng Qiu, Xin Wang, Dong Zhou, Zhaoyu Peng, Shan Wang, Yunfeng Long
article en
2 citations

Abstract

In response to the bus and main transformer tripping accident triggered by the isolation switch not closing in place at 500kV Huangping plant station, this paper combines onsite inspection, returning to the plant for disassembly and simulation analysis to systematically reveal the fault mechanism. It is found that the disconnecting switch motor blocking module coil breakage leads to the dynamic and static contacts not closing in place, which triggers the gap discharge and extra fast transient overvoltage (VFTO), and finally causes the thermal collapse of the circuit breaker voltage equalizing capacitor. The cumulative thermal effect of VFTO on the voltage-averaging capacitor is verified by electromagnetic transient simulation, and improvement measures for equipment manufacturing, condition monitoring and emergency response are proposed, which provide a theoretical basis for the operation and maintenance and design optimization of Gas Insulated Switchgear(GIS) equipment.

China Southern Power Grid (China) (CN)
Affordable and clean energy
Openalex Percentile: Top 11%
Geoscience and Mining Technology
2.61
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.