Study of flow and heat transfer characteristics of tandem cold plates for data center cooling

As data center chip power densities increase, liquid-cooling cold plates have gained widespread attention for their superior thermal management performance. This study systematically analyzes the thermal-hydraulic performance of tandem cold plates with different combination modes through numerical simulations and experimental validation. Results indicate that LCP2 (cold plate with narrow channel width) reduces thermal resistance ( R t ) by 29% compared to LCP1 (cold plate with wide channel width) but increases pressure drop ( ΔP ) by 141%. The LCP1+2 tandem mode combining a primary cold plate LCP1 and a secondary cold plate LCP2 achieves optimal thermal performance, which has a 3.49°C reduction in the maximum chip temperature ( T max ), 15% lower total thermal resistance ( R t, total ), and twofold improvement in thermal performance index ( TPI ) compared to LCP1+1 mode (two LCP1 tandem). In addition, as inlet temperature or load rate rises, increasing the flow rate can effectively reduce the temperature difference between two CPUs and improve system temperature uniformity. The deviation between the simulated data and the experimental data is within 2.32%, confirming the accuracy of the model. This work offers valuable insights for improving the cooling efficiency and thermal uniformity of liquid cooling systems, ensuring safe and reliable operation in high-performance data center environments.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2025-06-27
DOI
https://doi.org/10.1016/j.csite.2025.106590
Citations
7
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
4.99

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Study of flow and heat transfer characteristics of tandem cold plates for data center cooling

Xue Luo, Gongming Xin, Yang Chen, Jinbo Li et al.
7 citations
Case Studies in Thermal Engineering
Heat Transfer and Optimization
4.99
article

Study of flow and heat transfer characteristics of tandem cold plates for data center cooling

Xue Luo, Gongming Xin, Yang Chen, Jinbo Li, Chao‐Wei Chen, Man Wang, Zheng Zhang
article en
7 citations

Abstract

As data center chip power densities increase, liquid-cooling cold plates have gained widespread attention for their superior thermal management performance. This study systematically analyzes the thermal-hydraulic performance of tandem cold plates with different combination modes through numerical simulations and experimental validation. Results indicate that LCP2 (cold plate with narrow channel width) reduces thermal resistance ( R t ) by 29% compared to LCP1 (cold plate with wide channel width) but increases pressure drop ( ΔP ) by 141%. The LCP1+2 tandem mode combining a primary cold plate LCP1 and a secondary cold plate LCP2 achieves optimal thermal performance, which has a 3.49°C reduction in the maximum chip temperature ( T max ), 15% lower total thermal resistance ( R t, total ), and twofold improvement in thermal performance index ( TPI ) compared to LCP1+1 mode (two LCP1 tandem). In addition, as inlet temperature or load rate rises, increasing the flow rate can effectively reduce the temperature difference between two CPUs and improve system temperature uniformity. The deviation between the simulated data and the experimental data is within 2.32%, confirming the accuracy of the model. This work offers valuable insights for improving the cooling efficiency and thermal uniformity of liquid cooling systems, ensuring safe and reliable operation in high-performance data center environments.

Case Studies in Thermal EngineeringVol. 73
Shandong University (CN), Inspur (China) (CN)
Natural Science Foundation of Shandong Province
Affordable and clean energy
Openalex Percentile: Top 4%
Heat Transfer and Optimization
4.99
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.