Numerical study on the influence of louver design on VRF system thermal performance in enclosed spaces in Erbil city

Variable Refrigerant Flow (VRF) systems are extensively employed for space heating and cooling, particularly in multi-story buildings where outdoor units are discreetly placed behind aluminum louvers for architectural considerations. However, these metal louvers can hinder ventilation and heat rejection of the VRF air-conditioning outdoor unit, adversely affecting system performance. This impact manifests in elevated suction temperatures, increased energy consumption, and a diminished coefficient of system performance due to hot air recirculation behind the louvers. Additionally, the expelled hot discharge air from outdoor units rises, increasing the suction air temperature for the upper floors' VRF system. This numerical analysis study investigates the impact of louver tilt angle and opening ratio factors on the thermal performance of VRF air conditioners when installed on building balconies. The objective is to optimize louver designs for concealing condensing units, thereby enhancing overall performance and minimizing power consumption. Two proposed louver designs, incorporating varying tilt angles and opening ratios, are presented as solutions and compared with the existing design. The optimal solution to alleviate the unintended "stuck and stack effects" in the current design involves a proposed modification. The first option suggests decreasing the louver's tilt angle to 20° while maintaining a 60% opening ratio to lower suction temperatures and improve thermal performance. Additionally, increasing the louver opening ratio to 80% effectively reduces air recirculation, providing an alternative solution to optimize the overall performance of the VRF system. Comparisons with previous studies underscore local climate variations and operational disparities, emphasizing the need for tailored louver designs specific to environmental conditions.

Authors

Institutions

Publication Details

Journal
Al-Qadisiyah Journal for Engineering Sciences
Published
2025-06-24
DOI
https://doi.org/10.30772/qjes.2024.144970.1053
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Numerical study on the influence of louver design on VRF system thermal performance in enclosed spaces in Erbil city

Ramzi Raphael Ibraheem Barwari, Kawa Abdulghany Abdullah
Al-Qadisiyah Journal for Engineering Sciences
Building Energy and Comfort Optimization
article

Numerical study on the influence of louver design on VRF system thermal performance in enclosed spaces in Erbil city

Ramzi Raphael Ibraheem Barwari, Kawa Abdulghany Abdullah
article en

Abstract

Variable Refrigerant Flow (VRF) systems are extensively employed for space heating and cooling, particularly in multi-story buildings where outdoor units are discreetly placed behind aluminum louvers for architectural considerations. However, these metal louvers can hinder ventilation and heat rejection of the VRF air-conditioning outdoor unit, adversely affecting system performance. This impact manifests in elevated suction temperatures, increased energy consumption, and a diminished coefficient of system performance due to hot air recirculation behind the louvers. Additionally, the expelled hot discharge air from outdoor units rises, increasing the suction air temperature for the upper floors' VRF system. This numerical analysis study investigates the impact of louver tilt angle and opening ratio factors on the thermal performance of VRF air conditioners when installed on building balconies. The objective is to optimize louver designs for concealing condensing units, thereby enhancing overall performance and minimizing power consumption. Two proposed louver designs, incorporating varying tilt angles and opening ratios, are presented as solutions and compared with the existing design. The optimal solution to alleviate the unintended "stuck and stack effects" in the current design involves a proposed modification. The first option suggests decreasing the louver's tilt angle to 20° while maintaining a 60% opening ratio to lower suction temperatures and improve thermal performance. Additionally, increasing the louver opening ratio to 80% effectively reduces air recirculation, providing an alternative solution to optimize the overall performance of the VRF system. Comparisons with previous studies underscore local climate variations and operational disparities, emphasizing the need for tailored louver designs specific to environmental conditions.

Al-Qadisiyah Journal for Engineering SciencesVol. 18(2)
Salahaddin University-Erbil (IQ)
Affordable and clean energy
Openalex Percentile: Top 85%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Numerical study on the influence of louver design on VRF system thermal performance in enclosed spaces in Erbil city — Ramzi Raphael Ibraheem Barwari, Kawa Abdulghany Abdullah · Al-Qadisiyah Journal for Engineering Sciences (2025) | TGRS Research Map | TGRS