Effects of Ice Coating on the Maximum Discharge Distance During Ice-Shedding of Conductor-Ground Wire in 110 kV Transmission Lines

To address transmission line tripping caused by conductor-ground wire discharge induced by ice-shedding, this study developed a simulated 110 kV experimental platform to investigate ice-shedding discharge phenomena between conductors and ground wires. The research analyzed the impact of ice coating on the maximum discharge distance (MDD) and dynamically captured the arc evolution in conductor-ground wire gaps. Experimental results demonstrated that the MDD between an iced conductor and an uniced ground wire reached 14 cm under specific conditions, showing a 2–3 cm reduction compared to scenarios where both conductors and ground wires were iced under equivalent meteorological parameters. All measured values were below the 25 cm reference specified in the GB 50545-2010 standard. Synchronized analysis of arc characteristics and discharge current waveforms categorized the ice-shedding discharge process into four distinct phases: non-discharge, short-circuit arc, secondary arc, and insulation recovery, with a total arc duration of 61ms. Based on these findings, the study proposes utilizing image sensing resources from icing monitoring terminals in grid to detect ice-shedding discharge events in real time, providing a technical pathway for mitigating ice-related tripping risks in cold-region transmission systems.

Authors

Institutions

Publication Details

Published
2025-04-25
DOI
https://doi.org/10.1109/ceepe64987.2025.11033957
Citations
1
Primary Topic
Icing and De-icing Technologies
Type
article
Field-Weighted Citation Impact
4.99

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Effects of Ice Coating on the Maximum Discharge Distance During Ice-Shedding of Conductor-Ground Wire in 110 kV Transmission Lines

Lei Huang, Zengxin Pu, Zijian Wu, Yanpeng Hao et al.
1 citations
Icing and De-icing Technologies
4.99
article

Effects of Ice Coating on the Maximum Discharge Distance During Ice-Shedding of Conductor-Ground Wire in 110 kV Transmission Lines

Lei Huang, Zengxin Pu, Zijian Wu, Yanpeng Hao, Huan Huang, Yashuang Zheng
article en
1 citations

Abstract

To address transmission line tripping caused by conductor-ground wire discharge induced by ice-shedding, this study developed a simulated 110 kV experimental platform to investigate ice-shedding discharge phenomena between conductors and ground wires. The research analyzed the impact of ice coating on the maximum discharge distance (MDD) and dynamically captured the arc evolution in conductor-ground wire gaps. Experimental results demonstrated that the MDD between an iced conductor and an uniced ground wire reached 14 cm under specific conditions, showing a 2–3 cm reduction compared to scenarios where both conductors and ground wires were iced under equivalent meteorological parameters. All measured values were below the 25 cm reference specified in the GB 50545-2010 standard. Synchronized analysis of arc characteristics and discharge current waveforms categorized the ice-shedding discharge process into four distinct phases: non-discharge, short-circuit arc, secondary arc, and insulation recovery, with a total arc duration of 61ms. Based on these findings, the study proposes utilizing image sensing resources from icing monitoring terminals in grid to detect ice-shedding discharge events in real time, providing a technical pathway for mitigating ice-related tripping risks in cold-region transmission systems.

Guizhou Electric Power Design and Research Institute (CN), South China University of Technology (CN)
National Science and Technology Major Project
Openalex Percentile: Top 6%
Icing and De-icing Technologies
4.99
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Effects of Ice Coating on the Maximum Discharge Distance During Ice-Shedding of Conductor-Ground Wire in 110 kV Transmission Lines — Lei Huang, Zengxin Pu, et al. · (2025) | TGRS Research Map | TGRS