Renovation Methods for Atrium-Style Educational Buildings Based on Thermal Environment Testing in Cold Regions of China

While cold regions in China experience harsh winters, their summers also present significant overheating challenges in atrium-style buildings due to excessive solar gain. This study investigates the thermal environment of a non-ventilated atrium educational building located in a cold region of China, with tests conducted throughout the four seasons. The findings indicate that the atrium temperature is 1.7 °C, 1.1 °C, and 1.7 °C lower than that of the inner corridor during spring, autumn, and winter, respectively, but 0.6 °C higher in summer. From 7:00 a.m. to 10:00 p.m. on summer days, north-facing rooms with horizontal shading are 0.5 °C warmer than those facing south. A retrofit strategy that combines ventilated atrium shading with north-facing vertical shading is proposed, leading to a 0.7 °C reduction in atrium temperature and a 9.4% decrease in summer air conditioning energy consumption. Additionally, this study develops a retrofit framework for existing buildings, encompassing scope definition, diagnostics, strategy formulation, and evaluation to support high-quality renovations.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2025-06-17
DOI
https://doi.org/10.3390/buildings15122077
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Renovation Methods for Atrium-Style Educational Buildings Based on Thermal Environment Testing in Cold Regions of China

Kunming Li, Zhongxun Li, Xiao Liu, Hua Zhang et al.
Buildings
Building Energy and Comfort Optimization
article

Renovation Methods for Atrium-Style Educational Buildings Based on Thermal Environment Testing in Cold Regions of China

Kunming Li, Zhongxun Li, Xiao Liu, Hua Zhang, Jian Ma
article en

Abstract

While cold regions in China experience harsh winters, their summers also present significant overheating challenges in atrium-style buildings due to excessive solar gain. This study investigates the thermal environment of a non-ventilated atrium educational building located in a cold region of China, with tests conducted throughout the four seasons. The findings indicate that the atrium temperature is 1.7 °C, 1.1 °C, and 1.7 °C lower than that of the inner corridor during spring, autumn, and winter, respectively, but 0.6 °C higher in summer. From 7:00 a.m. to 10:00 p.m. on summer days, north-facing rooms with horizontal shading are 0.5 °C warmer than those facing south. A retrofit strategy that combines ventilated atrium shading with north-facing vertical shading is proposed, leading to a 0.7 °C reduction in atrium temperature and a 9.4% decrease in summer air conditioning energy consumption. Additionally, this study develops a retrofit framework for existing buildings, encompassing scope definition, diagnostics, strategy formulation, and evaluation to support high-quality renovations.

BuildingsVol. 15(12)
National University of Singapore (SG), Henan University of Technology (CN), Academy of National Food and Strategic Reserves Administration (CN), South China University of Technology (CN)
China Scholarship Council, Fundamental Research Funds for the Central Universities, Basic and Applied Basic Research Foundation of Guangdong Province
Openalex Percentile: Top 86%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.