Thermal management and heat transfer enhancement in air conditioning systems with chillers through smart control of chilled water backup systems

Air conditioning systems are significant contributors to electricity consumption in building operations, making thermal management and energy efficiency critical. This study focuses on enhancing the thermal performance and heat transfer efficiency of the chilled water system by implementing smart control of variable frequency chillers during low-load operations. Monthly cumulative cooling capacities and chilled water circulation data were analyzed, selecting January, February, March, November, and December for nighttime low-load energy-saving experiments. Regression models for each chiller were established, using indices such as R 2 , P-value, YIF, and average error rate of Y-values to validate the performance equations. Results demonstrated a significant positive correlation between load rate and chiller efficiency. During the selected months, operational data revealed efficiency improvements and energy-saving cumulative effects. The findings indicate that employing the chilled water interconnection pipeline system for load transfer increases chiller load rates, enhancing overall system efficiency and reducing the total power consumption of auxiliary equipment. The total energy saved during the operation amounted to 607,738 kWh, leading to a reduction in carbon emissions of 257,681 kg-CO 2 , equivalent to the annual carbon sequestration of Daan Forest Park (approximately 110.5 to 242.6 metric tons).

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2025-06-17
DOI
https://doi.org/10.1016/j.csite.2025.106527
Citations
1
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
1.01
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Thermal management and heat transfer enhancement in air conditioning systems with chillers through smart control of chilled water backup systems

Seyed Mohammad Vahidhosseini, Huimeng Ma, J.F. Chen, Saman Rashidi et al.
1 citations
Case Studies in Thermal Engineering
Building Energy and Comfort Optimization
1.01
article

Thermal management and heat transfer enhancement in air conditioning systems with chillers through smart control of chilled water backup systems

Seyed Mohammad Vahidhosseini, Huimeng Ma, J.F. Chen, Saman Rashidi, Wei‐Mon Yan, Chun-Han Li
article en
1 citations

Abstract

Air conditioning systems are significant contributors to electricity consumption in building operations, making thermal management and energy efficiency critical. This study focuses on enhancing the thermal performance and heat transfer efficiency of the chilled water system by implementing smart control of variable frequency chillers during low-load operations. Monthly cumulative cooling capacities and chilled water circulation data were analyzed, selecting January, February, March, November, and December for nighttime low-load energy-saving experiments. Regression models for each chiller were established, using indices such as R 2 , P-value, YIF, and average error rate of Y-values to validate the performance equations. Results demonstrated a significant positive correlation between load rate and chiller efficiency. During the selected months, operational data revealed efficiency improvements and energy-saving cumulative effects. The findings indicate that employing the chilled water interconnection pipeline system for load transfer increases chiller load rates, enhancing overall system efficiency and reducing the total power consumption of auxiliary equipment. The total energy saved during the operation amounted to 607,738 kWh, leading to a reduction in carbon emissions of 257,681 kg-CO 2 , equivalent to the annual carbon sequestration of Daan Forest Park (approximately 110.5 to 242.6 metric tons).

Case Studies in Thermal EngineeringVol. 73
National Taipei University of Technology (TW), University of Science and Technology (YE), Electronics Testing Center (TW), National Kaohsiung University of Science and Technology (TW), National Kaohsiung University of Applied Sciences (TW), Semnan University (IR)
Affordable and clean energy
Openalex Percentile: Top 24%
Building Energy and Comfort Optimization
1.01
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.