Enhanced Submodule Selection Algorithm for Mitigating FB-SM Overvoltage and HB-SM Undervoltage in Hybrid MMCs During DC Faults

Blocking all submodules (SMs) of hybrid modular multilevel converters (HMMCs) is a simple and rapid way to clear dc fault currents. However, full-bridge submodules (FB-SMs) must absorb nearly all of the fault energy stored in inductors and dc transmission lines, which can potentially cause significant FB-SM overvoltage when the transmission line is excessively long or the FB-SM ratio is low. In addition, half-bridge submodules (HB-SMs) are prone to undervoltage due to over-discharging before SM blocking, which hinders the HMMC’s restart. Current solutions, such as increasing SM capacitance and adding more FB-SMs, are not cost-effective. This article addresses the challenge of clearing dc fault currents in HMMCs by proposing an enhanced SM selection algorithm. Notably, the proposed method requires no additional hardware investment, does not disrupt normal system operation, and is compatible with existing FB-SM overvoltage mitigation techniques.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Industrial Electronics
Published
2025-06-17
DOI
https://doi.org/10.1109/tie.2025.3572923
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Enhanced Submodule Selection Algorithm for Mitigating FB-SM Overvoltage and HB-SM Undervoltage in Hybrid MMCs During DC Faults

Chao Gao, Xiongfeng Fang, Cheng Wang, Lei Li
IEEE Transactions on Industrial Electronics
HVDC Systems and Fault Protection
article

Enhanced Submodule Selection Algorithm for Mitigating FB-SM Overvoltage and HB-SM Undervoltage in Hybrid MMCs During DC Faults

Chao Gao, Xiongfeng Fang, Cheng Wang, Lei Li
article en

Abstract

Blocking all submodules (SMs) of hybrid modular multilevel converters (HMMCs) is a simple and rapid way to clear dc fault currents. However, full-bridge submodules (FB-SMs) must absorb nearly all of the fault energy stored in inductors and dc transmission lines, which can potentially cause significant FB-SM overvoltage when the transmission line is excessively long or the FB-SM ratio is low. In addition, half-bridge submodules (HB-SMs) are prone to undervoltage due to over-discharging before SM blocking, which hinders the HMMC’s restart. Current solutions, such as increasing SM capacitance and adding more FB-SMs, are not cost-effective. This article addresses the challenge of clearing dc fault currents in HMMCs by proposing an enhanced SM selection algorithm. Notably, the proposed method requires no additional hardware investment, does not disrupt normal system operation, and is compatible with existing FB-SM overvoltage mitigation techniques.

IEEE Transactions on Industrial ElectronicsVol. 72(12)
Chinese University of Hong Kong (HK), Nanjing University of Science and Technology (CN)
Openalex Percentile: Top 88%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies