Numerical Study on the Thermo-Electric Analysis of Carbonization in Epoxy Insulators

This study investigates the degradation of electrical insulation performance caused by carbonization in epoxy insulators used in high-voltage transmission systems. A numerical analysis was conducted using finite element analysis-based ANSYS Workbench and Q3D Extractor to evaluate changes in electric field intensity, current density, Joule heat, and charge density as the carbonized length increases. The results show that as carbonization progresses, the electric field intensity, current density, and Joule heat increase significantly, leading to a deterioration of insulation performance. When the carbonization length reaches 90 percent of the insulator, the electric field intensity sharply increases, indicating a critical degradation point. Complete carbonization penetrating the insulator results in insulation failure due to the formation of a conductive path, although dielectric breakdown does not occur under the rated operating voltage of 600V. These findings highlight the importance of early detection and monitoring of carbonization to prevent insulation failure in epoxy insulators.

Authors

Publication Details

Journal
The Transactions of The Korean Institute of Electrical Engineers
Published
2025-05-31
DOI
https://doi.org/10.5370/kiee.2025.74.5.878
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Numerical Study on the Thermo-Electric Analysis of Carbonization in Epoxy Insulators

Yun-Jae Lee, Shujun J. Zhang, Sangmin Nam
The Transactions of The Korean Institute of Electrical Engineers
High voltage insulation and dielectric phenomena
article

Numerical Study on the Thermo-Electric Analysis of Carbonization in Epoxy Insulators

Yun-Jae Lee, Shujun J. Zhang, Sangmin Nam
article en

Abstract

This study investigates the degradation of electrical insulation performance caused by carbonization in epoxy insulators used in high-voltage transmission systems. A numerical analysis was conducted using finite element analysis-based ANSYS Workbench and Q3D Extractor to evaluate changes in electric field intensity, current density, Joule heat, and charge density as the carbonized length increases. The results show that as carbonization progresses, the electric field intensity, current density, and Joule heat increase significantly, leading to a deterioration of insulation performance. When the carbonization length reaches 90 percent of the insulator, the electric field intensity sharply increases, indicating a critical degradation point. Complete carbonization penetrating the insulator results in insulation failure due to the formation of a conductive path, although dielectric breakdown does not occur under the rated operating voltage of 600V. These findings highlight the importance of early detection and monitoring of carbonization to prevent insulation failure in epoxy insulators.

The Transactions of The Korean Institute of Electrical EngineersVol. 74(5)
Openalex Percentile: Top 90%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.