Internal Voltage Equivalent RMS Models of Wind Generation for Transient Stability Assessment

Root-mean-square (RMS) simulations are time-efficient in studying transient stability of large-scale power systems with inverter-based resources (IBRs). However, existing RMS models of wind turbine generators (WTGs) have simplified DC bus dynamics and inner-loop voltage feedforward terms, resulting in reduced assessment accuracy. This paper develops a new internal voltage vector-based RMS model for Type-III WTGs and improves the existing internal voltage vector-based RMS model of Type-IV WTGs to accurately emulate synchronization dynamics under large-signal disturbances. Both WTG models integrate converter and control dynamics through equivalent circuits. For Type-III WTGs, the proposed model enables direct initialization of rotor variables, while for Type-IV WTGs, imperfect voltage feedforward and DC dynamics are incorporated to enhance accuracy. The proposed RMS models show desired performance in critical clearing time (CCT) assessment when compared to detailed EMT models.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Power Delivery
Published
2025-06-13
DOI
https://doi.org/10.1109/tpwrd.2025.3579678
Primary Topic
Energy Load and Power Forecasting
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Internal Voltage Equivalent RMS Models of Wind Generation for Transient Stability Assessment

Deepak Ramasubramanian, Evangelos Farantatos, Ilhan Koçar, Tao Xue et al.
IEEE Transactions on Power Delivery
Energy Load and Power Forecasting
article

Internal Voltage Equivalent RMS Models of Wind Generation for Transient Stability Assessment

Deepak Ramasubramanian, Evangelos Farantatos, Ilhan Koçar, Tao Xue, Mingxuan Zhao
article en

Abstract

Root-mean-square (RMS) simulations are time-efficient in studying transient stability of large-scale power systems with inverter-based resources (IBRs). However, existing RMS models of wind turbine generators (WTGs) have simplified DC bus dynamics and inner-loop voltage feedforward terms, resulting in reduced assessment accuracy. This paper develops a new internal voltage vector-based RMS model for Type-III WTGs and improves the existing internal voltage vector-based RMS model of Type-IV WTGs to accurately emulate synchronization dynamics under large-signal disturbances. Both WTG models integrate converter and control dynamics through equivalent circuits. For Type-III WTGs, the proposed model enables direct initialization of rotor variables, while for Type-IV WTGs, imperfect voltage feedforward and DC dynamics are incorporated to enhance accuracy. The proposed RMS models show desired performance in critical clearing time (CCT) assessment when compared to detailed EMT models.

IEEE Transactions on Power DeliveryVol. 40(5)
Electric Power Research Institute (US), Hong Kong Polytechnic University (HK), Polytechnique Montréal (CA)
Affordable and clean energy
Openalex Percentile: Top 88%
Energy Load and Power Forecasting
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.