Evaluation of Peak Electricity Load Effects from the Application of Sequential Cooling System Operations in Public Office Buildings

The Government of the Republic of Korea has implemented various policies targeting public office buildings to reduce peak electricity load and overall energy use in cooling. During periods of energy and power crises, sequential operation strategies for a cooling system are recommended to lower peak electricity demand in buildings. However, current sequential operations are typically implemented through cooling system shutdowns or arbitrary indoor temperature increases to reduce peak cooling electricity load. This study evaluated the effectiveness of different sequential cooling system operation strategies in public office buildings by analyzing their impact on peak cooling energy load and indoor thermal environment. Through simulation-based analysis, two main control approaches, traditional on/off control and set-back temperature control, were compared. Results demonstrated that while on/off control scenarios achieved a 64% reduction in peak cooling electricity load, these scenarios caused significant thermal discomfort and cooling load spikes upon system restart. In contrast, set-back control scenarios maintained indoor temperatures within the set-point range and reduced peak cooling electricity load by 8.7% while maintaining PMV values within approximately +0.5 compared to the common operation case. The set-back control strategy also prevented sudden cooling load increases observed in the on/off scenarios, offering a more balanced approach to energy management and occupant comfort in public office buildings.

Authors

Publication Details

Journal
Korean Journal of Air-Conditioning and Refrigeration Engineering
Published
2025-06-11
DOI
https://doi.org/10.6110/kjacr.2025.37.6.278
Primary Topic
Engineering Applied Research
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluation of Peak Electricity Load Effects from the Application of Sequential Cooling System Operations in Public Office Buildings

Beungyong Park, Chanuk Lee, Il Yeong Oh, Yujin Nam et al.
Korean Journal of Air-Conditioning and Refrigeration Engineering
Engineering Applied Research
article

Evaluation of Peak Electricity Load Effects from the Application of Sequential Cooling System Operations in Public Office Buildings

Beungyong Park, Chanuk Lee, Il Yeong Oh, Yujin Nam, Sung-Lok Do, Minho Kim, Ahmin Jang
article en

Abstract

The Government of the Republic of Korea has implemented various policies targeting public office buildings to reduce peak electricity load and overall energy use in cooling. During periods of energy and power crises, sequential operation strategies for a cooling system are recommended to lower peak electricity demand in buildings. However, current sequential operations are typically implemented through cooling system shutdowns or arbitrary indoor temperature increases to reduce peak cooling electricity load. This study evaluated the effectiveness of different sequential cooling system operation strategies in public office buildings by analyzing their impact on peak cooling energy load and indoor thermal environment. Through simulation-based analysis, two main control approaches, traditional on/off control and set-back temperature control, were compared. Results demonstrated that while on/off control scenarios achieved a 64% reduction in peak cooling electricity load, these scenarios caused significant thermal discomfort and cooling load spikes upon system restart. In contrast, set-back control scenarios maintained indoor temperatures within the set-point range and reduced peak cooling electricity load by 8.7% while maintaining PMV values within approximately +0.5 compared to the common operation case. The set-back control strategy also prevented sudden cooling load increases observed in the on/off scenarios, offering a more balanced approach to energy management and occupant comfort in public office buildings.

Korean Journal of Air-Conditioning and Refrigeration EngineeringVol. 37(6)
Openalex Percentile: Top 86%
Engineering Applied Research
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Evaluation of Peak Electricity Load Effects from the Application of Sequential Cooling System Operations in Public Office Buildings — Beungyong Park, Chanuk Lee, et al. · Korean Journal of Air-Conditioning and Refrigeration Engineering (2025) | TGRS Research Map | TGRS