Experimental validation of single-sided bottom-hung window ventilation models

• Experimental validation of 12 empirical models for bottom-hung window ventilation. • Conducted 80 tracer gas measurements under varied weather conditions. • Compared model designs and ventilation area definitions for bottom-hung windows. • Found significant discrepancies; most models underestimated airflow rates. In Europe, single-sided natural ventilation through bottom-hung windows is widely used to improve indoor air quality and thermal comfort in buildings. Despite the existence of numerous empirical models to estimate its airflow rates, there is a lack of experimental model validation for this specific window opening design. This study evaluates the design characteristics and accuracy of existing empirical models for single-sided bottom-hung window ventilation by summarizing 12 models from publications, standards, and handbooks, analyzing their discrepancies, and assessing their performance based on experimental measurements. These models were compared in terms of considered factors, ventilation area definitions, and model sensitivity. The experimental validation involved 80 tracer gas measurements conducted over four months in a full-scale test bench under various weather conditions. Results revealed significant discrepancies in model performance, with most models underestimating airflow rates. Models specifically designed for bottom-hung windows demonstrated higher accuracy, whereas adapted models from simplified openings showed varied accuracy depending on the ventilation area definition. European and German standards consistently underestimated airflow rates, potentially leading to oversizing of window geometries and increased energy consumption. Conversely, the ASHRAE model significantly overestimated airflow rates due to its inappropriate wind-driven ventilation coefficient. Our study concludes that empirical models must be tailored to the specific characteristics of bottom-hung window configurations. Accurate modeling requires precise ventilation area definitions and incorporation of both buoyancy-driven and wind-driven ventilation mechanisms. Future research should focus on refining these models through in-situ calibration to enhance their applicability across diverse conditions.

Authors

Institutions

Publication Details

Journal
Building and Environment
Published
2025-06-09
DOI
https://doi.org/10.1016/j.buildenv.2025.113253
Citations
1
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
1.01

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental validation of single-sided bottom-hung window ventilation models

Dirk Müller, Kai Rewitz, Jinzhi Jiang
1 citations
Building and Environment
Building Energy and Comfort Optimization
1.01
article

Experimental validation of single-sided bottom-hung window ventilation models

Dirk Müller, Kai Rewitz, Jinzhi Jiang
article en
1 citations

Abstract

• Experimental validation of 12 empirical models for bottom-hung window ventilation. • Conducted 80 tracer gas measurements under varied weather conditions. • Compared model designs and ventilation area definitions for bottom-hung windows. • Found significant discrepancies; most models underestimated airflow rates. In Europe, single-sided natural ventilation through bottom-hung windows is widely used to improve indoor air quality and thermal comfort in buildings. Despite the existence of numerous empirical models to estimate its airflow rates, there is a lack of experimental model validation for this specific window opening design. This study evaluates the design characteristics and accuracy of existing empirical models for single-sided bottom-hung window ventilation by summarizing 12 models from publications, standards, and handbooks, analyzing their discrepancies, and assessing their performance based on experimental measurements. These models were compared in terms of considered factors, ventilation area definitions, and model sensitivity. The experimental validation involved 80 tracer gas measurements conducted over four months in a full-scale test bench under various weather conditions. Results revealed significant discrepancies in model performance, with most models underestimating airflow rates. Models specifically designed for bottom-hung windows demonstrated higher accuracy, whereas adapted models from simplified openings showed varied accuracy depending on the ventilation area definition. European and German standards consistently underestimated airflow rates, potentially leading to oversizing of window geometries and increased energy consumption. Conversely, the ASHRAE model significantly overestimated airflow rates due to its inappropriate wind-driven ventilation coefficient. Our study concludes that empirical models must be tailored to the specific characteristics of bottom-hung window configurations. Accurate modeling requires precise ventilation area definitions and incorporation of both buoyancy-driven and wind-driven ventilation mechanisms. Future research should focus on refining these models through in-situ calibration to enhance their applicability across diverse conditions.

Building and EnvironmentVol. 282
RWTH Aachen University (DE)
Allianz Industrie Forschung, Bundesministerium für Wirtschaft und Energie
Affordable and clean energy
Openalex Percentile: Top 24%
Building Energy and Comfort Optimization
1.01
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.