Thermal Performance Evaluation of a Double Tube Ground Coupled Heat Exchanger in the Climate of Bangladesh

The ground-coupled heat exchanger (GCHE) is used in space heating and cooling systems to exchange heat with ground soil as a heat source/sink to reduce energy consumption. An experimental investigation is performed in this work to assess the thermal performance of a double tube ground coupled heat exchanger in the climate condition of Bangladesh. A double tube heat exchanger is fabricated using two PVC pipes of different diameter and inserted into 9.14 m depth of the ground. To measure the performance of the heat exchanger, water is circulated through the heat exchanger and temperatures and flow rate of the circulated water are measured. By altering the flow rate, the heat exchanger's rate of heat transfer can be determined. For a period of 12 hours, the water flow rates were 3 lit/min and 5 lit/min. The experiment shows that a flow rate of 3 lit/min gives a higher heat transfer rate per unit length than a flow rate of 5 lit/min. The average rate of heat transfer for the double tube GCHE was 82.36 W/m and 93.28 W/m for the flow rate of 5 lit/min and 3 lit/min, respectively, for the duration of 12 hours.

Authors

Institutions

Publication Details

Journal
SciEn Conference Series Engineering
Published
2025-05-07
DOI
https://doi.org/10.38032/scse.2025.1.27
Primary Topic
Geothermal Energy Systems and Applications
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Thermal Performance Evaluation of a Double Tube Ground Coupled Heat Exchanger in the Climate of Bangladesh

Adnan Abedeen, Raju Ahammad, Mohammad Ariful Islam, Al Rashedin Kawser
SciEn Conference Series Engineering
Geothermal Energy Systems and Applications
article

Thermal Performance Evaluation of a Double Tube Ground Coupled Heat Exchanger in the Climate of Bangladesh

Adnan Abedeen, Raju Ahammad, Mohammad Ariful Islam, Al Rashedin Kawser
article en

Abstract

The ground-coupled heat exchanger (GCHE) is used in space heating and cooling systems to exchange heat with ground soil as a heat source/sink to reduce energy consumption. An experimental investigation is performed in this work to assess the thermal performance of a double tube ground coupled heat exchanger in the climate condition of Bangladesh. A double tube heat exchanger is fabricated using two PVC pipes of different diameter and inserted into 9.14 m depth of the ground. To measure the performance of the heat exchanger, water is circulated through the heat exchanger and temperatures and flow rate of the circulated water are measured. By altering the flow rate, the heat exchanger's rate of heat transfer can be determined. For a period of 12 hours, the water flow rates were 3 lit/min and 5 lit/min. The experiment shows that a flow rate of 3 lit/min gives a higher heat transfer rate per unit length than a flow rate of 5 lit/min. The average rate of heat transfer for the double tube GCHE was 82.36 W/m and 93.28 W/m for the flow rate of 5 lit/min and 3 lit/min, respectively, for the duration of 12 hours.

SciEn Conference Series EngineeringVol. 1
Khulna University of Engineering and Technology (BD)
Openalex Percentile: Top 93%
Geothermal Energy Systems and Applications
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Thermal Performance Evaluation of a Double Tube Ground Coupled Heat Exchanger in the Climate of Bangladesh — Adnan Abedeen, Raju Ahammad, et al. · SciEn Conference Series Engineering (2025) | TGRS Research Map | TGRS