Partial Discharge-Based Cable Vulnerability Ranking with Fuzzy and FAHP Models: Application in a Danish Distribution Network

Aging underground cables pose a threatening issue in distribution systems. Replacing all cables at once is economically unfeasible, making it crucial to prioritize replacements. Traditionally, age-based strategies have been used, but they are likely to fail to depict the real condition of cables. Insulation faults are influenced by electrical, mechanical, thermal, and chemical stresses, and partial discharges (PDs) often serve as early indicators and accelerators of insulation aging. The trends in PD activity provide valuable information about insulation condition, although they do not directly reveal the cable's real age. Due to the absence of an established ranking methodology for such condition-based data, this paper proposes a fuzzy logic and fuzzy analytic hierarchy process (FAHP)-based cable vulnerability ranking framework that effectively manages uncertainty and expert-based conditions. The proposed framework requires only basic and readily accessible data inputs, specifically cable age, which utilities commonly maintain, and PD measurements, such as peak values and event counts, which can be acquired through cost-effective, noninvasive sensing methods. To systematically evaluate the method's performance and robustness, particularly given the inherent uncertainties in cable age and PD characteristics, this study employs Monte Carlo simulations coupled with a Spearman correlation analysis. The effectiveness of the developed framework is demonstrated using real operational cable data from a Danish distribution network, meteorological information from the Danish Meteorological Institute (DMI), and synthetically generated PD data. The results confirm that the FAHP-based ranking approach delivers robust and consistent outcomes under uncertainty, thereby supporting utilities in making more informed and economical maintenance decisions.

Authors

Institutions

Publication Details

Journal
Sensors
Published
2025-05-30
DOI
https://doi.org/10.3390/s25113454
Citations
3
Primary Topic
Power System Reliability and Maintenance
Type
article
Field-Weighted Citation Impact
3.91

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Partial Discharge-Based Cable Vulnerability Ranking with Fuzzy and FAHP Models: Application in a Danish Distribution Network

Hamid Mirshekali, Mohammad Reza Shadi, Hamid Reza Shaker
3 citations
Sensors
Power System Reliability and Maintenance
3.91
article

Partial Discharge-Based Cable Vulnerability Ranking with Fuzzy and FAHP Models: Application in a Danish Distribution Network

Hamid Mirshekali, Mohammad Reza Shadi, Hamid Reza Shaker
article en
3 citations

Abstract

Aging underground cables pose a threatening issue in distribution systems. Replacing all cables at once is economically unfeasible, making it crucial to prioritize replacements. Traditionally, age-based strategies have been used, but they are likely to fail to depict the real condition of cables. Insulation faults are influenced by electrical, mechanical, thermal, and chemical stresses, and partial discharges (PDs) often serve as early indicators and accelerators of insulation aging. The trends in PD activity provide valuable information about insulation condition, although they do not directly reveal the cable's real age. Due to the absence of an established ranking methodology for such condition-based data, this paper proposes a fuzzy logic and fuzzy analytic hierarchy process (FAHP)-based cable vulnerability ranking framework that effectively manages uncertainty and expert-based conditions. The proposed framework requires only basic and readily accessible data inputs, specifically cable age, which utilities commonly maintain, and PD measurements, such as peak values and event counts, which can be acquired through cost-effective, noninvasive sensing methods. To systematically evaluate the method's performance and robustness, particularly given the inherent uncertainties in cable age and PD characteristics, this study employs Monte Carlo simulations coupled with a Spearman correlation analysis. The effectiveness of the developed framework is demonstrated using real operational cable data from a Danish distribution network, meteorological information from the Danish Meteorological Institute (DMI), and synthetically generated PD data. The results confirm that the FAHP-based ranking approach delivers robust and consistent outcomes under uncertainty, thereby supporting utilities in making more informed and economical maintenance decisions.

SensorsVol. 25(11)
University of Southern Denmark (DK), Maersk (Denmark) (DK)
Energistyrelsen
Openalex Percentile: Top 7%
Power System Reliability and Maintenance
3.91
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.