Seat leak tests and commissioning of control valves in the cryogenic distribution system of the ESS superconducting linac

Abstract The European Spallation Source (ESS) is a neutron-scattering facility which will use a pulsed 2.0 GeV proton beam generated in the linear accelerator (LINAC) for releasing high-energy neutrons in the ESS target station. The 2K superconducting linac comprises 13 spoke and 30 elliptical cryomodules. The cryogenic distribution system (CDS) connects the cryogenic plant with the 43 cryomodules through a 400 meters long cryogenic multi-transfer, 43 valve boxes and an endbox. The CDS consists of 373 control valves in total. There are 8 and 10 control valves in each elliptical and spoke valve boxes, respectively, and 3 valves in the end box. The control valves are used for regulating or blocking the process helium flows. The seat tightness of the CDS valves is crucial especially for warming up individual cryomodules, which is required for potential short-term maintenance or repair activities in the cryomodule while keeping the others in cryogenic conditions. What is more, leaks over valve seats might cause moisture or ice formation on room temperature uninsulated pipes for warmup and cooldown valves or add heat load to the cryogenic system. Valve initialization and leak tightness tests were firstly performed with warm helium in the second half of 2022 before the first CDS cooldown. The tests revealed many leaks above the specified acceptable leak rate of 10 -4 mbarl/s with several of them reaching even 10 2 mbar.l/s. The major bulk of those leaks were fixed before and after the 2 nd CDS cooldown that followed in 2023. This paper describes the seat leak test method and results, as well as the possible causes of the observed leaks, the taken solutions for repairing the insufficiently tight valves and the prevention for valve seat leak.

Authors

Institutions

Publication Details

Journal
IOP Conference Series Materials Science and Engineering
Published
2025-05-01
DOI
https://doi.org/10.1088/1757-899x/1327/1/012016
Primary Topic
Superconducting Materials and Applications
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Seat leak tests and commissioning of control valves in the cryogenic distribution system of the ESS superconducting linac

Per Nilsson, J. Fydrych, J. Zhang, P Arnold et al.
IOP Conference Series Materials Science and Engineering
Superconducting Materials and Applications
article

Seat leak tests and commissioning of control valves in the cryogenic distribution system of the ESS superconducting linac

Per Nilsson, J. Fydrych, J. Zhang, P Arnold, J. Poliński, M. Chorowski
article en

Abstract

Abstract The European Spallation Source (ESS) is a neutron-scattering facility which will use a pulsed 2.0 GeV proton beam generated in the linear accelerator (LINAC) for releasing high-energy neutrons in the ESS target station. The 2K superconducting linac comprises 13 spoke and 30 elliptical cryomodules. The cryogenic distribution system (CDS) connects the cryogenic plant with the 43 cryomodules through a 400 meters long cryogenic multi-transfer, 43 valve boxes and an endbox. The CDS consists of 373 control valves in total. There are 8 and 10 control valves in each elliptical and spoke valve boxes, respectively, and 3 valves in the end box. The control valves are used for regulating or blocking the process helium flows. The seat tightness of the CDS valves is crucial especially for warming up individual cryomodules, which is required for potential short-term maintenance or repair activities in the cryomodule while keeping the others in cryogenic conditions. What is more, leaks over valve seats might cause moisture or ice formation on room temperature uninsulated pipes for warmup and cooldown valves or add heat load to the cryogenic system. Valve initialization and leak tightness tests were firstly performed with warm helium in the second half of 2022 before the first CDS cooldown. The tests revealed many leaks above the specified acceptable leak rate of 10 -4 mbarl/s with several of them reaching even 10 2 mbar.l/s. The major bulk of those leaks were fixed before and after the 2 nd CDS cooldown that followed in 2023. This paper describes the seat leak test method and results, as well as the possible causes of the observed leaks, the taken solutions for repairing the insufficiently tight valves and the prevention for valve seat leak.

IOP Conference Series Materials Science and EngineeringVol. 1327(1)
Wrocław University of Science and Technology (PL), European Spallation Source (SE), AGH University of Krakow (PL)
Openalex Percentile: Top 78%
Superconducting Materials and Applications
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.