Analysis of the temperature rising of 500 kV composite insulators

Abstract The heating defects of composite insulators pose a serious threat to the safe and stable operation of power transmission lines. A case of heating in composite insulators on a 500 kV transmission line was investigated, where two types of heating insulators on the line underwent visual inspection, infrared testing, dissection examination, hydrophobicity tests, permeability tests, water diffusion tests, and sealing tests. The defects and causes of heating in the composite insulators were analyzed. The results showed that both types of heating insulators exhibited poor adhesion between the core rod and sheath, and the water diffusion leakage current exceeded the standard value. This defect is the cause of the core rod deterioration and heating in the insulators. Operational maintenance recommendations were made based on these findings.

Authors

Institutions

Publication Details

Journal
Journal of Physics Conference Series
Published
2025-05-01
DOI
https://doi.org/10.1088/1742-6596/3011/1/012076
Primary Topic
Thermal Analysis in Power Transmission
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of the temperature rising of 500 kV composite insulators

Qijie Zhu, Ruixiang Tao, Xinlei Wu, Xianjin Yang et al.
3 links
Journal of Physics Conference Series
Thermal Analysis in Power Transmission
article

Analysis of the temperature rising of 500 kV composite insulators

Qijie Zhu, Ruixiang Tao, Xinlei Wu, Xianjin Yang, Jinbiao Ye, Te Li
article en

Abstract

Abstract The heating defects of composite insulators pose a serious threat to the safe and stable operation of power transmission lines. A case of heating in composite insulators on a 500 kV transmission line was investigated, where two types of heating insulators on the line underwent visual inspection, infrared testing, dissection examination, hydrophobicity tests, permeability tests, water diffusion tests, and sealing tests. The defects and causes of heating in the composite insulators were analyzed. The results showed that both types of heating insulators exhibited poor adhesion between the core rod and sheath, and the water diffusion leakage current exceeded the standard value. This defect is the cause of the core rod deterioration and heating in the insulators. Operational maintenance recommendations were made based on these findings.

Journal of Physics Conference SeriesVol. 3011(1)
State Grid Corporation of China (China) (CN), Shanghai Electric (China) (CN), Zhejiang Medicine (China) (CN)
Openalex Percentile: Top 88%
Thermal Analysis in Power Transmission
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.