Impedance Modeling for Line-Frequency Rectified Constant-Power Loads
Constant-power loads (CPLs) represent a growing presence on utility grids and microgrids. These power electronic loads are frequently configured as rectified loads operating from an ac input to produce a controlled dc output at a constant power level. This constant-power demand creates a well-known incremental negative input impedance that "fights" changes in grid voltage by demanding opposing changes in input current to maintain constant power operation for a load. Rectified CPLs can, therefore, create instabilities with relatively unique perturbations in the envelope of ac-side current and voltage. A system’s envelope response, characterized by the envelope impedance, has allowed for the application of traditional stability analysis techniques to rectified CPLs where complex nonlinear dynamics prevent the use of, e.g., small-signal approximations. This paper presents clear and experimentally useful definitions for envelope impedance, explains the limitations of traditional single-frequency perturbation stability analysis for rectified CPLs, develops new techniques for estimating rectified CPL input impedance using a double Fourier integral method, and demonstrates these techniques with both simulations and experimental results.
Authors
- Eric A. Ponce (ORCID: https://orcid.org/0000-0002-4755-0582)
- Steven B. Leeb (ORCID: https://orcid.org/0000-0002-3856-6005)
Institutions
- Massachusetts Institute of Technology (US)
Publication Details
- Journal
- IEEE Access
- Published
- 2025-01-01
- DOI
- https://doi.org/10.1109/access.2025.3572006
- Citations
- 3
- Primary Topic
- Electromagnetic Compatibility and Noise Suppression
- Type
- article
- Field-Weighted Citation Impact
- 2.19
Funders
- Office of Naval Research