Analysis of the Zero-Missing Phenomenon on Mixed Overhead-Underground Cables in 220 kV Transmission Lines
The paper investigates the dynamic behavior of a 220 kV mixed overhead-underground transmission line compensated with a shunt reactor, with a focus on the current zero-missing phenomenon and switching overvoltages. The zero-missing phenomenon, a condition in which the current through the circuit breaker fails to reach zero, can affect breaker operation and system stability, particularly in shunt-compensated systems. Key factors influencing this issue include cable length, cable configuration, reactive power compensation, and switching strategies. Using EMTP/ATP simulations based on a real grid model, the study evaluates various mitigation strategies for the zero-missing phenomenon, such as pre-insertion resistors, compensation ratios, and connections to high-power loads. Transient overvoltages on cable cores and sheaths during switching operations are also analyzed.
Institutions
- Hanoi University of Science and Technology (VN)
Publication Details
- Journal
- Smart Systems and Devices
- Published
- 2025-05-15
- DOI
- https://doi.org/10.51316/jst.182.ssad.2025.35.2.6
- Primary Topic
- Power Systems and Technologies
- Type
- article
- Field-Weighted Citation Impact
- 0.00
Funders
- Trường Đại học Bách Khoa Hà Nội