Improvement in Fire Resistance and Smoke Leakage Performance for Existing Polyvinyl Chloride Pipes Passing Through Walls
Penetration points on walls must include firestop measures to prevent the spread of fire. Countries worldwide have established standardized testing protocols for firestop methods, and firestop products must pass relevant tests before they can be used in buildings. In the present study, a simple method was developed to enhance the smoke leakage performance and fire resistance of existing polyvinyl chloride (PVC) pipes passing through walls. Two sets of smoke leakage tests were performed, followed by two sets of fire tests. The smoke leakage tests were nondestructive and thus did not damage the specimens; consequently, the same specimens could be used in the smoke leakage and fire tests. The results of the smoke leakage tests indicate that the method using PVC pipes wrapped with galvanized steel sleeves outperforms the method without such wrapping. Moreover, the results of the fire tests suggest that galvanized steel sleeves considerably improve thermal insulation and safety. This finding is explained as follows: PVC pipes may burn and break apart at high temperatures, compromising fire compartmentation. A galvanized steel sleeve can retain a burning, broken pipe piece, thereby preventing injuries and stopping the detached pipe from continuing to burn on the ground.
Authors
- T.K. Li
- Ching-Yuan Lin
- Tseng-Wei Chao
- Ying-Ji Chuang
Institutions
- National Taiwan University of Science and Technology (TW)
- Shih Hsin University (TW)
Publication Details
- Journal
- Fire
- Published
- 2025-05-19
- DOI
- https://doi.org/10.3390/fire8050202
- Primary Topic
- Fire dynamics and safety research
- Type
- article
- Field-Weighted Citation Impact
- 0.00