Performance of the new spatiotemporal airborne infection risk model across varied indoor air flowrates: An experimental study

• Revised Wells-Riley Model accounting for spatiotemporal modeling • A novel tracer-gas method to determine local purging flowrate is proposed • Model validated at varied airflow rates for mixing and displacement ventilation. • Flow dynamics and source position affect contaminant spread. • Customized mitigation measures are required per ventilation type. Understanding the complex dynamics of indoor airflows is crucial for mitigating airborne infection risks in ventilated spaces. These airflows can be simplified into two populations: Recirculating air that spreads contaminants and outgoing air that evacuates them. Quantifying these populations involves analyzing mass transfer between zones in the room/building. This study builds on the newly proposed model that enhances the Wells-Riley model by incorporating indoor airflow interaction mechanisms. The study explores the transfer probability between zones and the recirculation and purging flowrate at the target location and its impact on the risk of infection in a ventilated room. Our contributions include: (i) Performance evaluation of the revised model that accounts for transfer probabilities between zones and purging flowrates; (ii) a novel tracer-gas measurement method to determine local purging flowrates; and (iii) an analysis of how different ventilation systems interact with internal room flow. We validated the proposed model through experimental measurements in a climate chamber, examining contaminant source locations under varying ventilation rates using mixing ventilation (MV) and displacement ventilation (DV). Results reveal significant spatial and temporal heterogeneities in contaminant distribution, with MV showing pronounced temporal variability and DV exhibiting significant spatial variations. Under MV, purging flowrates increase with higher ventilation rates, whereas DV shows no such change. Our findings underscore the importance of considering airflow dynamics in ventilation design to effectively reduce contaminant transfer and/or airborne infection transmission.

Authors

Institutions

Publication Details

Journal
Building and Environment
Published
2025-05-18
DOI
https://doi.org/10.1016/j.buildenv.2025.113192
Citations
1
Primary Topic
Infection Control and Ventilation
Type
article
Field-Weighted Citation Impact
1.52

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Performance of the new spatiotemporal airborne infection risk model across varied indoor air flowrates: An experimental study

Harald Andersson, Mark Sundberg, Kazuhide Ito, Alan Kabanshi et al.
1 citations
Building and Environment
Infection Control and Ventilation
1.52
article

Performance of the new spatiotemporal airborne infection risk model across varied indoor air flowrates: An experimental study

Harald Andersson, Mark Sundberg, Kazuhide Ito, Alan Kabanshi, Ryu Itokazu, Mats Sandberg, Dario Senkic
article en
1 citations

Abstract

• Revised Wells-Riley Model accounting for spatiotemporal modeling • A novel tracer-gas method to determine local purging flowrate is proposed • Model validated at varied airflow rates for mixing and displacement ventilation. • Flow dynamics and source position affect contaminant spread. • Customized mitigation measures are required per ventilation type. Understanding the complex dynamics of indoor airflows is crucial for mitigating airborne infection risks in ventilated spaces. These airflows can be simplified into two populations: Recirculating air that spreads contaminants and outgoing air that evacuates them. Quantifying these populations involves analyzing mass transfer between zones in the room/building. This study builds on the newly proposed model that enhances the Wells-Riley model by incorporating indoor airflow interaction mechanisms. The study explores the transfer probability between zones and the recirculation and purging flowrate at the target location and its impact on the risk of infection in a ventilated room. Our contributions include: (i) Performance evaluation of the revised model that accounts for transfer probabilities between zones and purging flowrates; (ii) a novel tracer-gas measurement method to determine local purging flowrates; and (iii) an analysis of how different ventilation systems interact with internal room flow. We validated the proposed model through experimental measurements in a climate chamber, examining contaminant source locations under varying ventilation rates using mixing ventilation (MV) and displacement ventilation (DV). Results reveal significant spatial and temporal heterogeneities in contaminant distribution, with MV showing pronounced temporal variability and DV exhibiting significant spatial variations. Under MV, purging flowrates increase with higher ventilation rates, whereas DV shows no such change. Our findings underscore the importance of considering airflow dynamics in ventilation design to effectively reduce contaminant transfer and/or airborne infection transmission.

Building and EnvironmentVol. 281
Kyushu University (JP), University of Gävle (SE)
Svenska Forskningsrådet Formas
Openalex Percentile: Top 18%
Infection Control and Ventilation
1.52
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.