Sizing and designing of an adsorption chiller with phase change material thermal storage for an office building: Case study Nigeria

Nigeria receives an average of 6.29 kW/m²/day of solar radiation, making it ideal for solar-assisted cooling systems. In this study, a feasibility study of integrating solar-driven adsorption chiller was conducted for a 24 m³ office at the University of Nigeria, Nsukka using a silica gel-water pair. The prototype features a double-stage, 2-bed heat and mass recovery design with thermal energy storage as innovation to cover the mismatch between the day and night as well as during distrust time of solar collector. Results showed a cooling load of 2.7–3.5 kW, requiring a cooling capacity of 250 W/m² over 10 h with a performance coefficient (COP) of 0.68. A solar power input of 3.5–7.5 kW was achieved with an evacuated tube collector area of 1.75 m². The study validated the use of 28 kg of paraffin wax for heat storage and demonstrated a refrigeration capacity of 9406 kJ and cooling effect of 715.43 kJ with a cycle performance’s coefficient COPcy of 0.08 as well as specific cooling power (SCP) of 77 W/kg. This model offers a promising solution for sustainable cooling in Nigeria's climate especially and in Africa globally. However, the developed model can generate up to 8 kW cooling power with 23 kg of silica gel, which slightly exceeds the typical office size. This is characterized by the smallest office parameters that may affect the system’s performance due to the weather conditions. Thus, some parameters considered are slightly scaled up enabling the integration of more than one office. • A feasibility of integrating adsorption chiller in an office building was presented in University of Nigeria, Nsukka. • Thermal energy storage was added to cover the mismatch of the irradiance throughout the day. • A cooling load of 2.7-3.5 kW was found while COP of 0.56 was obtained. • An evacuated tube collector of 1.75m 2 was selected with a solar power of 3.5-7.5 kW.

Authors

Institutions

Publication Details

Journal
Next Energy
Published
2025-04-01
DOI
https://doi.org/10.1016/j.nxener.2025.100305
Citations
3
Primary Topic
Adsorption and Cooling Systems
Type
article
Field-Weighted Citation Impact
2.14

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Sizing and designing of an adsorption chiller with phase change material thermal storage for an office building: Case study Nigeria

C.N. Anyanwu, Fidelis I. Abam, Onyekwere Ojike, Mkpamdi Eke et al.
3 citations
Next Energy
Adsorption and Cooling Systems
2.14
article

Sizing and designing of an adsorption chiller with phase change material thermal storage for an office building: Case study Nigeria

C.N. Anyanwu, Fidelis I. Abam, Onyekwere Ojike, Mkpamdi Eke, Tagne Takote Brice Clausel
article en
3 citations

Abstract

Nigeria receives an average of 6.29 kW/m²/day of solar radiation, making it ideal for solar-assisted cooling systems. In this study, a feasibility study of integrating solar-driven adsorption chiller was conducted for a 24 m³ office at the University of Nigeria, Nsukka using a silica gel-water pair. The prototype features a double-stage, 2-bed heat and mass recovery design with thermal energy storage as innovation to cover the mismatch between the day and night as well as during distrust time of solar collector. Results showed a cooling load of 2.7–3.5 kW, requiring a cooling capacity of 250 W/m² over 10 h with a performance coefficient (COP) of 0.68. A solar power input of 3.5–7.5 kW was achieved with an evacuated tube collector area of 1.75 m². The study validated the use of 28 kg of paraffin wax for heat storage and demonstrated a refrigeration capacity of 9406 kJ and cooling effect of 715.43 kJ with a cycle performance’s coefficient COPcy of 0.08 as well as specific cooling power (SCP) of 77 W/kg. This model offers a promising solution for sustainable cooling in Nigeria's climate especially and in Africa globally. However, the developed model can generate up to 8 kW cooling power with 23 kg of silica gel, which slightly exceeds the typical office size. This is characterized by the smallest office parameters that may affect the system’s performance due to the weather conditions. Thus, some parameters considered are slightly scaled up enabling the integration of more than one office. • A feasibility of integrating adsorption chiller in an office building was presented in University of Nigeria, Nsukka. • Thermal energy storage was added to cover the mismatch of the irradiance throughout the day. • A cooling load of 2.7-3.5 kW was found while COP of 0.56 was obtained. • An evacuated tube collector of 1.75m 2 was selected with a solar power of 3.5-7.5 kW.

Next EnergyVol. 7
University of Nigeria (NG), University of Calabar (NG)
University Of Nigeria Nsukka
Openalex Percentile: Top 14%
Adsorption and Cooling Systems
2.14
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.