Harmonic Distortion Analysis and Mitigation in an On-Grid Wind Farm using Passive Filters: A Case Study on the Shahat Distribution Network

The numerous non-linear power electronic components in a wind energy conversion system (WECS) cause harmonic distortion, which diminishes the quality of the electricity produced. For WECS to function optimally with the power grid, these distortions must not exceed the limits established by international standards for total harmonic distortion (THD) in voltage and current waveforms. As required by current rules, this study looks at the harmonic distortion at the point of common coupling (PCC) between a planned 10.5 MW wind farm and the SHAHAT distribution network in northeastern Libya. MATLAB/Simulink is employed to simulate the wind farm conversion units and execute harmonic elimination with passive harmonic filters (PHFs). The frequency spectrum and THD findings at the PCC are assessed in compliance with the IEEE 519 standard. The results demonstrated the significant efficacy of PHFs in reducing low-order harmonics below 2 kHz while being ineffectual in the supra-harmonic zone. The findings of this study are juxtaposed with analogous literature, and the outcomes of this comparison are delineated.

Authors

Publication Details

Journal
Journal of Information Systems Engineering & Management
Published
2025-05-08
DOI
https://doi.org/10.52783/jisem.v10i44s.8661
Citations
1
Primary Topic
Power System Optimization and Stability
Type
article
Field-Weighted Citation Impact
0.73
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Harmonic Distortion Analysis and Mitigation in an On-Grid Wind Farm using Passive Filters: A Case Study on the Shahat Distribution Network

Saad T. Y. Alfalahi
1 citations
Journal of Information Systems Engineering & Management
Power System Optimization and Stability
0.73
article

Harmonic Distortion Analysis and Mitigation in an On-Grid Wind Farm using Passive Filters: A Case Study on the Shahat Distribution Network

Saad T. Y. Alfalahi
article en
1 citations

Abstract

The numerous non-linear power electronic components in a wind energy conversion system (WECS) cause harmonic distortion, which diminishes the quality of the electricity produced. For WECS to function optimally with the power grid, these distortions must not exceed the limits established by international standards for total harmonic distortion (THD) in voltage and current waveforms. As required by current rules, this study looks at the harmonic distortion at the point of common coupling (PCC) between a planned 10.5 MW wind farm and the SHAHAT distribution network in northeastern Libya. MATLAB/Simulink is employed to simulate the wind farm conversion units and execute harmonic elimination with passive harmonic filters (PHFs). The frequency spectrum and THD findings at the PCC are assessed in compliance with the IEEE 519 standard. The results demonstrated the significant efficacy of PHFs in reducing low-order harmonics below 2 kHz while being ineffectual in the supra-harmonic zone. The findings of this study are juxtaposed with analogous literature, and the outcomes of this comparison are delineated.

Journal of Information Systems Engineering & ManagementVol. 10(44s)
Openalex Percentile: Top 29%
Power System Optimization and Stability
0.73
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.