Pilot protection based on voltage and current correlation for DC lines in mesh DC grid without boundary

As the scale of DC grids expands, the converter will be connected with multiple outgoing lines. In this context, locating current-limiting reactors at the outlet of the converter can effectively balance the contradiction between current-limiting requirements and construction costs. However, the absence of a clear line boundary poses challenges for DC line protection. In response, a setting-less line pilot protection is proposed for the mesh DC grid without boundary. First, through the analysis of measured impedance characteristics, it is found that for internal faults, the high-frequency voltage and high-frequency current on both ends of the line are negatively correlated. Whereas for external faults, there is at least one end of the line where the high-frequency voltage and high-frequency current are positively correlated. Then, a suitable high-pass filter is designed, and the cosine similarity is utilized to evaluate whether the filtered voltage and current waveforms display a similar trend of change, further providing a comprehensive protection scheme. Finally, numerous simulation results demonstrate that the proposed method exhibits strong endurance to fault resistance and noise environment. The proposed method remains applicable even when system parameters change and does not require complex setting.

Authors

Publication Details

Journal
International Journal of Electrical Power & Energy Systems
Published
2025-05-09
DOI
https://doi.org/10.1016/j.ijepes.2025.110723
Citations
3
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
2.19
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Pilot protection based on voltage and current correlation for DC lines in mesh DC grid without boundary

Xu Shi, Zhihui Dai
3 citations
International Journal of Electrical Power & Energy Systems
HVDC Systems and Fault Protection
2.19
article

Pilot protection based on voltage and current correlation for DC lines in mesh DC grid without boundary

Xu Shi, Zhihui Dai
article en
3 citations

Abstract

As the scale of DC grids expands, the converter will be connected with multiple outgoing lines. In this context, locating current-limiting reactors at the outlet of the converter can effectively balance the contradiction between current-limiting requirements and construction costs. However, the absence of a clear line boundary poses challenges for DC line protection. In response, a setting-less line pilot protection is proposed for the mesh DC grid without boundary. First, through the analysis of measured impedance characteristics, it is found that for internal faults, the high-frequency voltage and high-frequency current on both ends of the line are negatively correlated. Whereas for external faults, there is at least one end of the line where the high-frequency voltage and high-frequency current are positively correlated. Then, a suitable high-pass filter is designed, and the cosine similarity is utilized to evaluate whether the filtered voltage and current waveforms display a similar trend of change, further providing a comprehensive protection scheme. Finally, numerous simulation results demonstrate that the proposed method exhibits strong endurance to fault resistance and noise environment. The proposed method remains applicable even when system parameters change and does not require complex setting.

International Journal of Electrical Power & Energy SystemsVol. 168
Affordable and clean energy
Openalex Percentile: Top 12%
HVDC Systems and Fault Protection
2.19
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Pilot protection based on voltage and current correlation for DC lines in mesh DC grid without boundary — Xu Shi, Zhihui Dai · International Journal of Electrical Power & Energy Systems (2025) | TGRS Research Map | TGRS