A single-ended protection scheme for the hybrid MTDC power grid using traveling wave peak-to-decline ratio

• The peak-to-decline ratio is introduced to construct the protection criteria. • The high-resistance fault identification capability and the anti-noise capability are improved using the peak-to-decline ratio, which reaches 800 Ω and 40 dB, respectively. • The ratio calculation is simple for the computer. The total time required for the identification period is estimated to be 0.8 ms, which meets the requirements of the rapidity for the main protection scheme. • Only a 10 kHz sampling frequency is required in the proposed protection scheme, which is an advantage compared with other protection schemes. For multi-terminal HVDC(MTDC) power grids, boundary elements may not exist at the transmission line terminal, which makes traditional traveling wave protection schemes unsuitable. Furthermore, most traveling wave protection schemes require a high sampling frequency to detect the traveling wave heads and are not sensitive to the high-resistance ground fault. To solve these problems, a single-ended protection scheme using the traveling wave peak-to-decline ratio is proposed in this research. The 1-mode traveling wave propagation characteristics of different measuring points are first analyzed. Then, the peak-to-decline ratio and the change value of the 1-mode traveling wave are applied to construct the fault line identification criterion at the end of the DC line and the common point between two DC lines, respectively. Finally, the proposed protection scheme is verified by a hybrid three-terminal HVDC power grid. Results show that the proposed protection scheme only requires a 10 kHz sampling frequency, and the ground fault with 800 Ω fault resistance or 40 dB noise interference can be identified correctly.

Authors

Institutions

Publication Details

Journal
International Journal of Electrical Power & Energy Systems
Published
2025-05-01
DOI
https://doi.org/10.1016/j.ijepes.2025.110702
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A single-ended protection scheme for the hybrid MTDC power grid using traveling wave peak-to-decline ratio

Zijiang Wang, Youping Fan, Zhaoyi Zhang, Jianbin Fan et al.
International Journal of Electrical Power & Energy Systems
HVDC Systems and Fault Protection
article

A single-ended protection scheme for the hybrid MTDC power grid using traveling wave peak-to-decline ratio

Zijiang Wang, Youping Fan, Zhaoyi Zhang, Jianbin Fan, Xinyue Zheng
article en

Abstract

• The peak-to-decline ratio is introduced to construct the protection criteria. • The high-resistance fault identification capability and the anti-noise capability are improved using the peak-to-decline ratio, which reaches 800 Ω and 40 dB, respectively. • The ratio calculation is simple for the computer. The total time required for the identification period is estimated to be 0.8 ms, which meets the requirements of the rapidity for the main protection scheme. • Only a 10 kHz sampling frequency is required in the proposed protection scheme, which is an advantage compared with other protection schemes. For multi-terminal HVDC(MTDC) power grids, boundary elements may not exist at the transmission line terminal, which makes traditional traveling wave protection schemes unsuitable. Furthermore, most traveling wave protection schemes require a high sampling frequency to detect the traveling wave heads and are not sensitive to the high-resistance ground fault. To solve these problems, a single-ended protection scheme using the traveling wave peak-to-decline ratio is proposed in this research. The 1-mode traveling wave propagation characteristics of different measuring points are first analyzed. Then, the peak-to-decline ratio and the change value of the 1-mode traveling wave are applied to construct the fault line identification criterion at the end of the DC line and the common point between two DC lines, respectively. Finally, the proposed protection scheme is verified by a hybrid three-terminal HVDC power grid. Results show that the proposed protection scheme only requires a 10 kHz sampling frequency, and the ground fault with 800 Ω fault resistance or 40 dB noise interference can be identified correctly.

International Journal of Electrical Power & Energy SystemsVol. 168
Wuhan University (CN), Wuhan Business University (CN), Wuhan University of Science and Technology (CN), Capital University of Economics and Business (CN)
Key Technologies Research and Development Program
Affordable and clean energy
Openalex Percentile: Top 93%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.