Effects of Germicidal UV Air Disinfection Devices on Indoor Air Quality in an Unoccupied Aged Care Facility

The COVID-19 pandemic has precipitated renewed interest in germicidal ultraviolet (GUV) for indoor air disinfection. However, UV-C radiation from these devices can produce indoor air pollutants including ozone, oxygenated volatile organic compounds (OVOCs), and ultrafine particles. A month-long study of indoor air quality effects of GUV was undertaken in an unoccupied aged care facility in Melbourne, Australia under both mechanical ventilation (∼3 air changes h–1) and natural ventilation (∼1 h–1) conditions. Upper room GUV-254 and whole room GUV-222 devices were tested. GUV-222 produced ∼670 μg/h of ozone resulting in <1 ppb enhancements in indoor ozone. GUV-222 also produced small increases in OVOCs, particularly acetic acid and methanol, that were <1 ppb with mechanical ventilation, and <2 ppb with natural ventilation. Small acetaldehyde enhancements (∼0.1 ppb) were associated with GUV-254. GUV was not associated with changes in indoor particles. GUV-222 and -254 initiated OVOC enhancements were insensitive to indoor ozone but exhibited strong temperature and humidity sensitivities, suggesting UV-initiated surface chemistry rather than gas phase chemistry as the key driver of GUV OVOC enhancements. Overall, ventilation and changes in outdoor pollutants had substantial effects, while GUV produced small but measurable effects on indoor air quality in a real-world urban setting.

Authors

Institutions

Publication Details

Journal
ACS ES&T Air
Published
2025-04-29
DOI
https://doi.org/10.1021/acsestair.4c00322
Citations
4
Primary Topic
Infection Control and Ventilation
Type
article
Field-Weighted Citation Impact
6.07

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Effects of Germicidal UV Air Disinfection Devices on Indoor Air Quality in an Unoccupied Aged Care Facility

Jason Monty, Vinay Menon, Suman Majumdar, Amanda J. Wheeler et al.
4 citations
ACS ES&T Air
Infection Control and Ventilation
6.07
article

Effects of Germicidal UV Air Disinfection Devices on Indoor Air Quality in an Unoccupied Aged Care Facility

Jason Monty, Vinay Menon, Suman Majumdar, Amanda J. Wheeler, Erin Dunne, Simon A. Joosten, Lídia Morawska, Ruhi S. Humphries, James Harnwell, Emily Barnes Franklin, Caleb Mynard, Jason Ward, Michelle Delaire, Dylan Lynton
article en
4 citations

Abstract

The COVID-19 pandemic has precipitated renewed interest in germicidal ultraviolet (GUV) for indoor air disinfection. However, UV-C radiation from these devices can produce indoor air pollutants including ozone, oxygenated volatile organic compounds (OVOCs), and ultrafine particles. A month-long study of indoor air quality effects of GUV was undertaken in an unoccupied aged care facility in Melbourne, Australia under both mechanical ventilation (∼3 air changes h–1) and natural ventilation (∼1 h–1) conditions. Upper room GUV-254 and whole room GUV-222 devices were tested. GUV-222 produced ∼670 μg/h of ozone resulting in <1 ppb enhancements in indoor ozone. GUV-222 also produced small increases in OVOCs, particularly acetic acid and methanol, that were <1 ppb with mechanical ventilation, and <2 ppb with natural ventilation. Small acetaldehyde enhancements (∼0.1 ppb) were associated with GUV-254. GUV was not associated with changes in indoor particles. GUV-222 and -254 initiated OVOC enhancements were insensitive to indoor ozone but exhibited strong temperature and humidity sensitivities, suggesting UV-initiated surface chemistry rather than gas phase chemistry as the key driver of GUV OVOC enhancements. Overall, ventilation and changes in outdoor pollutants had substantial effects, while GUV produced small but measurable effects on indoor air quality in a real-world urban setting.

ACS ES&T AirVol. 2(6)
CSIRO Oceans and Atmosphere (AU), Goulburn Valley Health (AU), Burnet Institute (AU), Queensland University of Technology (AU), The University of Melbourne (AU), Government of Victoria (AU), Australian Regenerative Medicine Institute (AU), University of Surrey (GB), Physical Sciences (United States) (US), Monash University (AU)
Department of Health and Human Services, State Government of Victoria
Openalex Percentile: Top 4%
Infection Control and Ventilation
6.07
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.