ABSTRACT Data centers worldwide face rising electricity consumption, with a substantial portion used for cooling IT components. Traditional air‐cooling methods have become increasingly inefficient as server power densities rise, causing a transition towards liquid‐cooling technologies. Direct liquid‐cooled servers operate at higher coolant temperatures than air‐cooled systems, significantly reducing cooling demands and improving the potential for waste heat reuse. However, elevated coolant temperatures may increase server power consumption, reduce heat transfer to the coolant, and potentially affect IT equipment performance. To systematically quantify these effects, a comprehensive analysis based on benchmark tests was conducted on ten liquid‐cooled servers under varying coolant inlet temperatures (25°C–50°C) and IT loads. Results demonstrated that server performance remained unaffected within this temperature range. Nonetheless, raising the average cooling temperature from 30°C to 50°C increased server power consumption by 8.5% and reduced heat transfer to the coolant by 14.6% due to thermal losses. Based on these experimental results, a simulation model was developed and implemented in TRNSYS. This model enables the prediction of the behavior of direct liquid‐cooled servers and the assessment of practical applications for waste heat utilization.

Authors

Institutions

Publication Details

Journal
Energy Science & Engineering
Published
2025-04-27
DOI
https://doi.org/10.1002/ese3.70116
Citations
2
Primary Topic
Cloud Computing and Resource Management
Type
article
Field-Weighted Citation Impact
6.49

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Data Centers With Direct Liquid‐Cooled Servers: Experimental Analysis and Modeling

Markus Sekulla, Axel Auweter, Thorsten Urbaneck, Maximilian Stahlhut et al.
2 citations
Energy Science & Engineering
Cloud Computing and Resource Management
6.49
article

Data Centers With Direct Liquid‐Cooled Servers: Experimental Analysis and Modeling

Markus Sekulla, Axel Auweter, Thorsten Urbaneck, Maximilian Stahlhut, Peter Großöhme
article en
2 citations

Abstract

ABSTRACT Data centers worldwide face rising electricity consumption, with a substantial portion used for cooling IT components. Traditional air‐cooling methods have become increasingly inefficient as server power densities rise, causing a transition towards liquid‐cooling technologies. Direct liquid‐cooled servers operate at higher coolant temperatures than air‐cooled systems, significantly reducing cooling demands and improving the potential for waste heat reuse. However, elevated coolant temperatures may increase server power consumption, reduce heat transfer to the coolant, and potentially affect IT equipment performance. To systematically quantify these effects, a comprehensive analysis based on benchmark tests was conducted on ten liquid‐cooled servers under varying coolant inlet temperatures (25°C–50°C) and IT loads. Results demonstrated that server performance remained unaffected within this temperature range. Nonetheless, raising the average cooling temperature from 30°C to 50°C increased server power consumption by 8.5% and reduced heat transfer to the coolant by 14.6% due to thermal losses. Based on these experimental results, a simulation model was developed and implemented in TRNSYS. This model enables the prediction of the behavior of direct liquid‐cooled servers and the assessment of practical applications for waste heat utilization.

Energy Science & EngineeringVol. 13(7)
Chemnitz University of Technology (DE)
Bundesministerium für Bildung und Forschung, Projektträger Jülich
Openalex Percentile: Top 4%
Cloud Computing and Resource Management
6.49
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.