Statistical Analysis of Protection Current Transformer Performance Based on Error Ratio and Knee Voltage on 20 kV Feeder at Bangka Transmission and Substation Service Unit

Current Transformers (CTs) are essential components in power system protection, ensuring accurate current measurement for relay operations.. This study evaluates the accuracy of protection CTs used in 20kV feeders at the Bangka Transmission and Substation Service Unit. Measurements were conducted on CTs with 5 and 7 years of usage to analyze ratio error and knee voltage compliance with IEC 61869-2 standards. The results indicate that all CTs meet the standard, with ratio errors below 1% and knee voltages exceeding 60V. Normality tests confirmed that the data are normally distributed, allowing statistical analysis using t-tests. The t-test results showed no significant difference in ratio error and knee voltage between CTs used for 5 and 7 years. This study concludes that aging over this period does not significantly affect CT accuracy, ensuring continued reliability in power system protection.

Authors

Institutions

Publication Details

Journal
Jurnal Ecotipe (Electronic Control Telecommunication Information and Power Engineering)
Published
2025-04-24
DOI
https://doi.org/10.33019/jurnalecotipe.v12i1.4558
Primary Topic
Electrical Fault Detection and Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Statistical Analysis of Protection Current Transformer Performance Based on Error Ratio and Knee Voltage on 20 kV Feeder at Bangka Transmission and Substation Service Unit

Welly Yandi, Rudy Kurniawan, Asmar Asmar, Maisa Sapitri
1 links
Jurnal Ecotipe (Electronic Control Telecommunication Information and Power Engineering)
Electrical Fault Detection and Protection
article

Statistical Analysis of Protection Current Transformer Performance Based on Error Ratio and Knee Voltage on 20 kV Feeder at Bangka Transmission and Substation Service Unit

Welly Yandi, Rudy Kurniawan, Asmar Asmar, Maisa Sapitri
article en

Abstract

Current Transformers (CTs) are essential components in power system protection, ensuring accurate current measurement for relay operations.. This study evaluates the accuracy of protection CTs used in 20kV feeders at the Bangka Transmission and Substation Service Unit. Measurements were conducted on CTs with 5 and 7 years of usage to analyze ratio error and knee voltage compliance with IEC 61869-2 standards. The results indicate that all CTs meet the standard, with ratio errors below 1% and knee voltages exceeding 60V. Normality tests confirmed that the data are normally distributed, allowing statistical analysis using t-tests. The t-test results showed no significant difference in ratio error and knee voltage between CTs used for 5 and 7 years. This study concludes that aging over this period does not significantly affect CT accuracy, ensuring continued reliability in power system protection.

Jurnal Ecotipe (Electronic Control Telecommunication Information and Power Engineering)Vol. 12(1)
University of Bangka Belitung (ID)
Affordable and clean energy
Openalex Percentile: Top 93%
Electrical Fault Detection and Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.