Heat exchanger control: Performance of thermodynamics-based geometrical vs classical PID controllers
In this communication, a control problem based on thermodynamic principles is developed to control the output temperature of a heat exchanger in an experimental setup. The system is controlled through a nonlinear output error, which is proportional to the total entropy production within the heat exchanger. A lumped-parameter model of the heat exchanger allows to define the thermodynamic control scheme, with geometric control principles, a high-gain observer and an anti-windup scheme, which provides robustness against parametric uncertainties and disturbances. To make a comparison with classical control schemes, a Ziegler–Nichols PID controller was tuned for a First Order Plus Dead Time plant approximation. The experimental setup used a National Instruments Compact FieldPoint controller, and the control scheme was programmed in a LabVIEW interface. The performance of the proposed controller was tested under two criteria: energetic performance and total tracking control error. The results show that the classical controller has a better energy-saving performance, while the thermodynamic controller has a better tracking performance, making it more suitable for applications where temperature control needs to be more precise.
Authors
- Marco A. Zárate-Navarro (ORCID: https://orcid.org/0000-0001-7415-8503)
- Omar R. Gómez-Gómez
- J.P. García-Sandoval (ORCID: https://orcid.org/0000-0001-6889-0140)
Publication Details
- Journal
- Case Studies in Thermal Engineering
- Published
- 2025-04-24
- DOI
- https://doi.org/10.1016/j.csite.2025.106130
- Citations
- 1
- Primary Topic
- Control and Stability of Dynamical Systems
- Type
- article
- Field-Weighted Citation Impact
- 1.21
Funders
- Consejo Nacional de Ciencia y Tecnología