Impact of phase shifting transformers on distance protection and fault ride-through scheme

• The impact of a PST on the calculated impedance of the distance relay is analyzed. • The impact of small phase-shifting adjustments (within ± 10°) on distance protection is little. • Large phase-shifting adjustments (beyond ± 10°) can lead to mal-operation. • A novel FRT scheme is proposed to deal with the challenge arising from large phase-shifting adjustments. The phase shifting transformer (PST) serves as an important power flow control device that adjusts power flow by altering the phase of voltages at its terminals. This adjustment can affect the distance protection of lines equipped with PST, potentially leading to mal-operation of distance protection. To address this issue, this paper analyzes the impact of a PST on the calculated impedance of the distance relay and conducts a detailed analysis of the adaptability of distance protection in lines equipped with a PST, revealing that the phase shifting range is the primary factor affecting distance protection. The analysis indicates that the impact of small phase-shifting adjustments (within ± 10°) on distance protection is little, while large phase-shifting adjustments (beyond ± 10°) can lead to mal-operation. To deal with the challenges caused by large phase-shifting adjustments, a novel fault ride-through (FRT) scheme that employs an additional hardware loop is proposed in this paper. When a line fault is occurred, the additional hardware loop is triggered to ensure the quick isolation and safety of the PST. This FRT scheme guarantees that distance protection functions correctly, even during large phase-shifting adjustments. The effectiveness and feasibility of the proposed scheme are validated through simulations.

Authors

Institutions

Publication Details

Journal
International Journal of Electrical Power & Energy Systems
Published
2025-04-23
DOI
https://doi.org/10.1016/j.ijepes.2025.110688
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Impact of phase shifting transformers on distance protection and fault ride-through scheme

Cong Sui, Xiaoxiao Liu, Jianjun Yu, Tao Zheng et al.
International Journal of Electrical Power & Energy Systems
Power Systems Fault Detection
article

Impact of phase shifting transformers on distance protection and fault ride-through scheme

Cong Sui, Xiaoxiao Liu, Jianjun Yu, Tao Zheng, You Shen
article en

Abstract

• The impact of a PST on the calculated impedance of the distance relay is analyzed. • The impact of small phase-shifting adjustments (within ± 10°) on distance protection is little. • Large phase-shifting adjustments (beyond ± 10°) can lead to mal-operation. • A novel FRT scheme is proposed to deal with the challenge arising from large phase-shifting adjustments. The phase shifting transformer (PST) serves as an important power flow control device that adjusts power flow by altering the phase of voltages at its terminals. This adjustment can affect the distance protection of lines equipped with PST, potentially leading to mal-operation of distance protection. To address this issue, this paper analyzes the impact of a PST on the calculated impedance of the distance relay and conducts a detailed analysis of the adaptability of distance protection in lines equipped with a PST, revealing that the phase shifting range is the primary factor affecting distance protection. The analysis indicates that the impact of small phase-shifting adjustments (within ± 10°) on distance protection is little, while large phase-shifting adjustments (beyond ± 10°) can lead to mal-operation. To deal with the challenges caused by large phase-shifting adjustments, a novel fault ride-through (FRT) scheme that employs an additional hardware loop is proposed in this paper. When a line fault is occurred, the additional hardware loop is triggered to ensure the quick isolation and safety of the PST. This FRT scheme guarantees that distance protection functions correctly, even during large phase-shifting adjustments. The effectiveness and feasibility of the proposed scheme are validated through simulations.

International Journal of Electrical Power & Energy SystemsVol. 168
North China Electric Power University (CN), Directorate-General for Energy (BE), University of Edinburgh (GB), KU Leuven (BE)
National Natural Science Foundation of China
Sustainable cities and communities
Openalex Percentile: Top 91%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.