Inherent thermodynamic performance assessment of a variable refrigerant flow system under transient cooling load: A case study of an eco-villa

Variable refrigerant flow systems are recognized for their energy efficiency, yet their performance under fluctuating cooling loads and interdependencies among intrinsic performance variables remains insufficiently explored. This study investigates the thermodynamic and environmental performance of a variable refrigerant flow system for an eco-villa in Masdar City, Abu Dhabi, under dynamic operating conditions. A mathematical model exhibiting a coefficient of determination of 0.89, a mean absolute error of 0.04, and a mean square error of 0.01, has been developed in MATLAB to evaluate system behavior. Analysis of the system's intrinsic performance variables reveals its ability to dynamically adjust compressor speed in response to fluctuating cooling loads, enhancing isentropic efficiency. This dynamic adaptability results in a reduction in power consumption by 11.1 % and an enhancement in the coefficient of performance by 12.5 % during minimum load conditions compared to constant-speed compressors. Energy and exergy evaluations indicate that cooling load profiles dominate system performance. Compressor power ranges from 6.06 kW at peak load conditions to 2.64 kW at minimum load conditions, with the corresponding increase in the coefficient of performance (3.73–4.40) and exergy efficiency (36.91 %–43.58 %), and a decrease in exergy destruction (2.95–1.05 kW). Statistical analysis using Pearson correlation highlights strong interdependencies among variables, including ambient temperature's positive correlation with compressor speed (0.89) and condensation temperature's negative correlation with isentropic efficiency (−0.22). Conversely, evaporation temperature shows a positive correlation with isentropic efficiency (0.29), enhancing system performance and reducing exergy destruction. Finally, the environmental evaluation analysis a 15.38 % reduction in annual energy consumption and a 1.51-ton reduction in carbon dioxide emissions per eco-villa annually, scaling to 1509.75 tons for 1000 villas, underscoring the system's potential for energy efficiency and environmental sustainability.

Authors

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2025-04-22
DOI
https://doi.org/10.1016/j.csite.2025.106171
Citations
1
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
1.01
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Inherent thermodynamic performance assessment of a variable refrigerant flow system under transient cooling load: A case study of an eco-villa

Muhammad Reshaeel, Mohamed I. Hassan Ali
1 citations
Case Studies in Thermal Engineering
Building Energy and Comfort Optimization
1.01
article

Inherent thermodynamic performance assessment of a variable refrigerant flow system under transient cooling load: A case study of an eco-villa

Muhammad Reshaeel, Mohamed I. Hassan Ali
article en
1 citations

Abstract

Variable refrigerant flow systems are recognized for their energy efficiency, yet their performance under fluctuating cooling loads and interdependencies among intrinsic performance variables remains insufficiently explored. This study investigates the thermodynamic and environmental performance of a variable refrigerant flow system for an eco-villa in Masdar City, Abu Dhabi, under dynamic operating conditions. A mathematical model exhibiting a coefficient of determination of 0.89, a mean absolute error of 0.04, and a mean square error of 0.01, has been developed in MATLAB to evaluate system behavior. Analysis of the system's intrinsic performance variables reveals its ability to dynamically adjust compressor speed in response to fluctuating cooling loads, enhancing isentropic efficiency. This dynamic adaptability results in a reduction in power consumption by 11.1 % and an enhancement in the coefficient of performance by 12.5 % during minimum load conditions compared to constant-speed compressors. Energy and exergy evaluations indicate that cooling load profiles dominate system performance. Compressor power ranges from 6.06 kW at peak load conditions to 2.64 kW at minimum load conditions, with the corresponding increase in the coefficient of performance (3.73–4.40) and exergy efficiency (36.91 %–43.58 %), and a decrease in exergy destruction (2.95–1.05 kW). Statistical analysis using Pearson correlation highlights strong interdependencies among variables, including ambient temperature's positive correlation with compressor speed (0.89) and condensation temperature's negative correlation with isentropic efficiency (−0.22). Conversely, evaporation temperature shows a positive correlation with isentropic efficiency (0.29), enhancing system performance and reducing exergy destruction. Finally, the environmental evaluation analysis a 15.38 % reduction in annual energy consumption and a 1.51-ton reduction in carbon dioxide emissions per eco-villa annually, scaling to 1509.75 tons for 1000 villas, underscoring the system's potential for energy efficiency and environmental sustainability.

Case Studies in Thermal EngineeringVol. 71
Affordable and clean energy
Openalex Percentile: Top 26%
Building Energy and Comfort Optimization
1.01
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.