Evaluation of different subcooling arrangements in a CO2 refrigeration plant using extractions from the flash-gas tank

• Two subcooling configurations were tested in a CO 2 refrigeration system. • Subcooling is achieved by extracting refrigerant from the flash-gas tank. • An operational map was created to identify the optimal working conditions. • Liquid extraction improved COP by 9.4% and reduced optimal pressure by 3.0 bar. • Vapour extraction increased COP by 7.5% and reduced optimal pressure by 2.5 bar. Carbon dioxide (CO 2 ) is a widely used natural refrigerant with a low critical temperature (∼31 °C), that makes necessary the use of complex cycle arrangements to enhance the performance of refrigerating plants, especially at high ambient temperatures. Considering this, the present work evaluates two simple subcooling arrangements experimentally based on stream extractions from the flash-gas tank installed between the back-pressure valve and the thermostatic expansion valve. These extractions are expanded in a subcooler installed at the exit of the gas-cooler, providing the subcooling effect depending on the tank pressure and the fluid extracted (liquid or vapour). Since the flash-gas tank pressure introduces a new degree of freedom, an optimisation process for maximising the COP is mandatory depending on the heat-rejection conditions (temperature and pressure). Therefore, this work presents the optimisation process for three heat-rejection temperatures (28, 31 and 34 °C) using extractions from vapour or liquid, reaching COP improvements up to 9.4 % with optimal pressure reductions of up to 3.0 bar.

Authors

Institutions

Publication Details

Journal
International Journal of Refrigeration
Published
2025-04-20
DOI
https://doi.org/10.1016/j.ijrefrig.2025.03.037
Citations
2
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
1.43
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluation of different subcooling arrangements in a CO2 refrigeration plant using extractions from the flash-gas tank

Francisco Vidan Falomir, R. Larrondo-Sancho, Ramón Cabello, Daniel Sánchez
2 citations
International Journal of Refrigeration
Refrigeration and Air Conditioning Technologies
1.43
article

Evaluation of different subcooling arrangements in a CO2 refrigeration plant using extractions from the flash-gas tank

Francisco Vidan Falomir, R. Larrondo-Sancho, Ramón Cabello, Daniel Sánchez
article en
2 citations

Abstract

• Two subcooling configurations were tested in a CO 2 refrigeration system. • Subcooling is achieved by extracting refrigerant from the flash-gas tank. • An operational map was created to identify the optimal working conditions. • Liquid extraction improved COP by 9.4% and reduced optimal pressure by 3.0 bar. • Vapour extraction increased COP by 7.5% and reduced optimal pressure by 2.5 bar. Carbon dioxide (CO 2 ) is a widely used natural refrigerant with a low critical temperature (∼31 °C), that makes necessary the use of complex cycle arrangements to enhance the performance of refrigerating plants, especially at high ambient temperatures. Considering this, the present work evaluates two simple subcooling arrangements experimentally based on stream extractions from the flash-gas tank installed between the back-pressure valve and the thermostatic expansion valve. These extractions are expanded in a subcooler installed at the exit of the gas-cooler, providing the subcooling effect depending on the tank pressure and the fluid extracted (liquid or vapour). Since the flash-gas tank pressure introduces a new degree of freedom, an optimisation process for maximising the COP is mandatory depending on the heat-rejection conditions (temperature and pressure). Therefore, this work presents the optimisation process for three heat-rejection temperatures (28, 31 and 34 °C) using extractions from vapour or liquid, reaching COP improvements up to 9.4 % with optimal pressure reductions of up to 3.0 bar.

International Journal of RefrigerationVol. 175
Universitat Jaume I (ES)
Openalex Percentile: Top 21%
Refrigeration and Air Conditioning Technologies
1.43
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.