Simulation analysis of transformer main protection maloperation caused by current transformer saturation

Abstract A BC-phase short-circuit grounding fault occurred on the 35kV Xiaai line at the 110kV Xiajiaka substation in a specific power grid. This fault caused an incorrect operation of the differential instantaneous protection of the 110kV Xiajiaka #1 transformer. Theoretical analysis suggests that this maloperation may have been caused by the simultaneous action of the line protection during the fault, which led to the saturation of the protection CT on the medium-voltage side of the transformer. To thoroughly investigate the cause of the incident, a detailed electromagnetic transient simulation model was developed using PSCAD. The simulation results revealed that the maloperation of the #1 transformer differential protection was primarily due to two factors: the differing voltage states at the time of the two fault occurrences and the remanence in the CT. The overlap of the line protection action with the fault triggered the saturation of the medium-voltage side CT, leading to the maloperation of the differential protection. These simulation results, based on a realistic grid fault scenario, are crucial for analyzing similar incidents and enhancing the safe and reliable operation of power grids.

Authors

Institutions

Publication Details

Journal
Journal of Physics Conference Series
Published
2025-04-01
DOI
https://doi.org/10.1088/1742-6596/2993/1/012055
Citations
1
Primary Topic
Advanced Decision-Making Techniques
Type
article
Field-Weighted Citation Impact
3.25
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Simulation analysis of transformer main protection maloperation caused by current transformer saturation

Lijun Lei, Zhiyuan Luo, Jiangbo Xu, Junjie Zhang et al.
1 citations
Journal of Physics Conference Series
Advanced Decision-Making Techniques
3.25
article

Simulation analysis of transformer main protection maloperation caused by current transformer saturation

Lijun Lei, Zhiyuan Luo, Jiangbo Xu, Junjie Zhang, Han Wang, Ru Li
article en
1 citations

Abstract

Abstract A BC-phase short-circuit grounding fault occurred on the 35kV Xiaai line at the 110kV Xiajiaka substation in a specific power grid. This fault caused an incorrect operation of the differential instantaneous protection of the 110kV Xiajiaka #1 transformer. Theoretical analysis suggests that this maloperation may have been caused by the simultaneous action of the line protection during the fault, which led to the saturation of the protection CT on the medium-voltage side of the transformer. To thoroughly investigate the cause of the incident, a detailed electromagnetic transient simulation model was developed using PSCAD. The simulation results revealed that the maloperation of the #1 transformer differential protection was primarily due to two factors: the differing voltage states at the time of the two fault occurrences and the remanence in the CT. The overlap of the line protection action with the fault triggered the saturation of the medium-voltage side CT, leading to the maloperation of the differential protection. These simulation results, based on a realistic grid fault scenario, are crucial for analyzing similar incidents and enhancing the safe and reliable operation of power grids.

Journal of Physics Conference SeriesVol. 2993(1)
Electric Power Research Institute (US), State Grid Corporation of China (China) (CN), Economic Research Institute (BG)
Openalex Percentile: Top 10%
Advanced Decision-Making Techniques
3.25
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Simulation analysis of transformer main protection maloperation caused by current transformer saturation — Lijun Lei, Zhiyuan Luo, et al. · Journal of Physics Conference Series (2025) | TGRS Research Map | TGRS