Behavior of a 10kVA Single-Phase Dry Transformer Under Diverse Lightning Impulses: A Simulation Approach
This paper presents a simulation-based model of a 10 kVA, 33 kV/415 V, single-phase dry transformer subjected to standard as well as non-standard lightning impulse voltages. The analysis of the transformer's subsequent responses is then described. Dry-type transformers are known for their safety, low maintenance requirements, lack of pollution, ease of installation, environmental friendliness, and fire protection features. However, non-standard lightning impulse voltages can have a detrimental impact on electrical insulation. For this reason, electrical equipment typically undergoes a lightning impulse voltage test using a standardized waveform (1.2 × 50 μs) after manufacturing. Recognizing that real-world lightning strikes often deviate from this standard waveform, a simulation model of a real-life 10 kVA, 33 kV/415 V single-phase dry transformer was developed to understand the behaviour of insulation under non-standard impulse voltages. This model was then used to analyze the transformer's response to both standard (SLI) and non-standard lightning impulse (NSLI) waveforms.
Authors
- Biswendu Chatterjee (ORCID: https://orcid.org/0000-0001-9817-0435)
- Soumyadeep Maity (ORCID: https://orcid.org/0000-0002-0490-4985)
- B. Chakraborty (ORCID: https://orcid.org/0000-0001-7384-1255)
- Sovan Dalai (ORCID: https://orcid.org/0000-0001-5991-1237)
- Saibal Chatterjee (ORCID: https://orcid.org/0000-0003-1680-7565)
- Subhajit Maur (ORCID: https://orcid.org/0000-0002-5736-2841)
- Pradipta Ghosh (ORCID: https://orcid.org/0000-0002-0051-4859)
Institutions
- University of Engineering & Management (IN)
- Jadavpur University (IN)
- Government of Mizoram (IN)
Publication Details
- Published
- 2024-10-25
- DOI
- https://doi.org/10.1109/giest62955.2024.10959922
- Citations
- 1
- Primary Topic
- Power Transformer Diagnostics and Insulation
- Type
- article
- Field-Weighted Citation Impact
- 0.21