Performance evaluation of an energy-efficient oscillating air-conditioning dehumidification system through experimental testing and numerical modelling

This study examines the performance of a new oscillating air-conditioning dehumidification system, designed to overcome the limitations of traditional methods, such as energy-intensive defrost cycles and inconsistent dehumidification in high-humidity conditions. Experimental tests demonstrate that the system achieves a dew point as low as −9.38°C with specific humidity reaching to 1.67 g/kg and coefficient of performance (COP) ranging from 3.3 to 4.7. Apart from testing, numerical modelling of the system has been built in TRNSYS and validated using experimental data. A validated TRNSYS model was used to extend the analysis across various climate zones, revealing that the system performs optimally in high-humidity regions like Hong Kong and Chongqing, with an annual average COP of 3.89 in Hong Kong. In contrast, colder and drier regions like Urumqi maintained lower but stable energy efficiency, with an annual average COP of 2.30. These findings suggest that the oscillating air-conditioning dehumidification system offers versatile, climate-adaptable operation with potential applications in diverse building types. Practical Application This study’s findings offer built environment professionals an air-conditioning dehumidification solution suited to diverse climate conditions. The oscillating air-conditioning system, with its continuous dehumidification capability and optimised energy efficiency with COP of 3.89 in high-humidity regions, provides an approach for deep dehumidification in demanding environments. By reducing reliance on energy-intensive defrost cycles, this system is ideal for applications in commercial and industrial settings, such as healthcare facilities and battery manufacturing centres, where precise humidity control is critical.

Authors

Institutions

Publication Details

Journal
Building Services Engineering Research and Technology
Published
2025-04-08
DOI
https://doi.org/10.1177/01436244251333135
Primary Topic
Adsorption and Cooling Systems
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Performance evaluation of an energy-efficient oscillating air-conditioning dehumidification system through experimental testing and numerical modelling

Zhichu Wang, Cheng Zeng, Xiangjun Shang, Zhi Pei et al.
Building Services Engineering Research and Technology
Adsorption and Cooling Systems
article

Performance evaluation of an energy-efficient oscillating air-conditioning dehumidification system through experimental testing and numerical modelling

Zhichu Wang, Cheng Zeng, Xiangjun Shang, Zhi Pei, Jun Lü, Jing Qin, Liang Liu, J. Yue
article en

Abstract

This study examines the performance of a new oscillating air-conditioning dehumidification system, designed to overcome the limitations of traditional methods, such as energy-intensive defrost cycles and inconsistent dehumidification in high-humidity conditions. Experimental tests demonstrate that the system achieves a dew point as low as −9.38°C with specific humidity reaching to 1.67 g/kg and coefficient of performance (COP) ranging from 3.3 to 4.7. Apart from testing, numerical modelling of the system has been built in TRNSYS and validated using experimental data. A validated TRNSYS model was used to extend the analysis across various climate zones, revealing that the system performs optimally in high-humidity regions like Hong Kong and Chongqing, with an annual average COP of 3.89 in Hong Kong. In contrast, colder and drier regions like Urumqi maintained lower but stable energy efficiency, with an annual average COP of 2.30. These findings suggest that the oscillating air-conditioning dehumidification system offers versatile, climate-adaptable operation with potential applications in diverse building types. Practical Application This study’s findings offer built environment professionals an air-conditioning dehumidification solution suited to diverse climate conditions. The oscillating air-conditioning system, with its continuous dehumidification capability and optimised energy efficiency with COP of 3.89 in high-humidity regions, provides an approach for deep dehumidification in demanding environments. By reducing reliance on energy-intensive defrost cycles, this system is ideal for applications in commercial and industrial settings, such as healthcare facilities and battery manufacturing centres, where precise humidity control is critical.

Building Services Engineering Research and TechnologyVol. 46(4)
Chongqing University (CN), University of Hull (GB), China Electric Equipment Group (China) (CN)
National Natural Science Foundation of China
Openalex Percentile: Top 94%
Adsorption and Cooling Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.