Cementitious versus alkali-activated textile-reinforced mortars combined with mineral wool insulation for strengthening masonry panels exposed to high temperature

This study focuses on the experimental investigation of an integrated system that combines seismic upgrading of masonry load-bearing elements with their protection against fire-born high temperatures. Two systems of carbon textile-reinforced mortar (TRM) comprising different matrices were combined with mineral wool panels. The first matrix was a cementitious mortar with polymers based on ordinary Portland cement (OPC), while the second one was an environmentally friendly alkali-activated mortar (AAM) based on ferronickel slag. The study focused on the mechanical performance of retrofitted masonry specimens in terms of shear bond capacity, out-of-plane monotonic and in-plane cyclic bending capacity. Prior to their mechanical testing, some of the retrofitted specimens (both thermally protected and not) were exposed to 600 °C for 1.5 h. It was concluded that: (i) the residual (post-heat) shear bond capacity of both the thermally protected and unprotected masonry-to-TRM joints remains unaffected or decreases in case of prisms furnished with textile-reinforced alkali-activated or polymer-modified mortar overlays, respectively; (ii) exposure to high temperatures bears a moderate negative effect on the flexural response of the TRM-retrofitted-insulated walls irrespective of the matrix type; (iii) textile-reinforced alkali-activated mortar jackets comprise a promising retrofitting option for flexure-deficient walls without any thermal protection means. • Heat does not affect shear bond strength of insulated/bare TRAAM-retrofitted prism. • Heat reduces shear bond strength of insulated/bare TRCM-retrofitted prism. • Heat degrades moderately flexural response of TRM-retrofitted-insulated wall. • TRAAM can be a potential strengthening and insulating overlay of bending walls.

Authors

Institutions

Publication Details

Journal
Construction and Building Materials
Published
2025-04-06
DOI
https://doi.org/10.1016/j.conbuildmat.2025.141133
Citations
3
Primary Topic
Masonry and Concrete Structural Analysis
Type
article
Field-Weighted Citation Impact
2.86

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Cementitious versus alkali-activated textile-reinforced mortars combined with mineral wool insulation for strengthening masonry panels exposed to high temperature

Paraskevi D. Askouni, Catherine G. Papanicolaou, Thanasis Triantafillou, Panagiotis Kapsalis
3 citations
Construction and Building Materials
Masonry and Concrete Structural Analysis
2.86
article

Cementitious versus alkali-activated textile-reinforced mortars combined with mineral wool insulation for strengthening masonry panels exposed to high temperature

Paraskevi D. Askouni, Catherine G. Papanicolaou, Thanasis Triantafillou, Panagiotis Kapsalis
article en
3 citations

Abstract

This study focuses on the experimental investigation of an integrated system that combines seismic upgrading of masonry load-bearing elements with their protection against fire-born high temperatures. Two systems of carbon textile-reinforced mortar (TRM) comprising different matrices were combined with mineral wool panels. The first matrix was a cementitious mortar with polymers based on ordinary Portland cement (OPC), while the second one was an environmentally friendly alkali-activated mortar (AAM) based on ferronickel slag. The study focused on the mechanical performance of retrofitted masonry specimens in terms of shear bond capacity, out-of-plane monotonic and in-plane cyclic bending capacity. Prior to their mechanical testing, some of the retrofitted specimens (both thermally protected and not) were exposed to 600 °C for 1.5 h. It was concluded that: (i) the residual (post-heat) shear bond capacity of both the thermally protected and unprotected masonry-to-TRM joints remains unaffected or decreases in case of prisms furnished with textile-reinforced alkali-activated or polymer-modified mortar overlays, respectively; (ii) exposure to high temperatures bears a moderate negative effect on the flexural response of the TRM-retrofitted-insulated walls irrespective of the matrix type; (iii) textile-reinforced alkali-activated mortar jackets comprise a promising retrofitting option for flexure-deficient walls without any thermal protection means. • Heat does not affect shear bond strength of insulated/bare TRAAM-retrofitted prism. • Heat reduces shear bond strength of insulated/bare TRCM-retrofitted prism. • Heat degrades moderately flexural response of TRM-retrofitted-insulated wall. • TRAAM can be a potential strengthening and insulating overlay of bending walls.

Construction and Building MaterialsVol. 474
University of Patras (GR), Hellenic Ministry of Culture and Sports (GR)
Hellenic Foundation for Research and Innovation
Openalex Percentile: Top 11%
Masonry and Concrete Structural Analysis
2.86
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.