The Effect of Aluminum Wire Winding Patterns on Partial Discharge Occurrence in 24 kV Insulator Strings

This study investigates Partial Discharge (PD) on aluminum wire insulators for 24 kV transmission lines. Using the IEC 60270 charge measurement, PD was evaluated on line post 57-2, line post 57-3, and pin post 56/57-2 insulators. A metallic pipe modeled the transmission line, with aluminum wire wound in straight and curved patterns as per Thailand's PEA standards. A test voltage of 10–25 kV was applied, and the Phase Resolved Partial Discharge (PRPD) analysis identified corona discharge as the primary PD type. The results showed increased PD magnitude and frequency at higher voltages, peaking at 90° and 270° phase angles. In addition, the pin post insulator and straight winding produced the highest PD. This study highlights the impact of wire winding patterns on PD, an often-overlooked factor. The simple, cost-effective evaluation method provides insights for optimizing insulation, maintenance, and real-time monitoring in high-voltage systems, benefiting applications such as cable spacers and lightning arresters.

Authors

Publication Details

Journal
Engineering Technology & Applied Science Research
Published
2025-04-03
DOI
https://doi.org/10.48084/etasr.10223
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

The Effect of Aluminum Wire Winding Patterns on Partial Discharge Occurrence in 24 kV Insulator Strings

Nutthaphong Tanthanuch, Nopadol Uchaipichat, Sirirod Srisomchai
Engineering Technology & Applied Science Research
High voltage insulation and dielectric phenomena
article

The Effect of Aluminum Wire Winding Patterns on Partial Discharge Occurrence in 24 kV Insulator Strings

Nutthaphong Tanthanuch, Nopadol Uchaipichat, Sirirod Srisomchai
article en

Abstract

This study investigates Partial Discharge (PD) on aluminum wire insulators for 24 kV transmission lines. Using the IEC 60270 charge measurement, PD was evaluated on line post 57-2, line post 57-3, and pin post 56/57-2 insulators. A metallic pipe modeled the transmission line, with aluminum wire wound in straight and curved patterns as per Thailand's PEA standards. A test voltage of 10–25 kV was applied, and the Phase Resolved Partial Discharge (PRPD) analysis identified corona discharge as the primary PD type. The results showed increased PD magnitude and frequency at higher voltages, peaking at 90° and 270° phase angles. In addition, the pin post insulator and straight winding produced the highest PD. This study highlights the impact of wire winding patterns on PD, an often-overlooked factor. The simple, cost-effective evaluation method provides insights for optimizing insulation, maintenance, and real-time monitoring in high-voltage systems, benefiting applications such as cable spacers and lightning arresters.

Engineering Technology & Applied Science ResearchVol. 15(2)
Openalex Percentile: Top 95%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

The Effect of Aluminum Wire Winding Patterns on Partial Discharge Occurrence in 24 kV Insulator Strings — Nutthaphong Tanthanuch, Nopadol Uchaipichat, et al. · Engineering Technology & Applied Science Research (2025) | TGRS Research Map | TGRS