This study addresses the issue of excessive cooling in data center server rooms caused by the sparse deployment of server cabinets. A precise air-conditioning control strategy based on the working temperature response of target cabinets is proposed. CFD software is used to establish the server room model and set control objectives. The simulations reveal that, under the condition of ensuring normal operation and equipment safety in the data center, the supply air temperature of the CRAC (computer room air conditioner) system can be adjusted to provide more flexibility, thereby reducing energy consumption. Based on this strategy, the dynamic load of the server room is simulated to obtain the supply air temperature of the CRAC system, forming a simulation dataset. A graph structure is created based on the distribution characteristics of the servers, and a regression prediction model for the supply air temperature of the CRAC system is trained using graph neural networks. The results show that, in the test set, 95.8% of the predicted supply air temperature errors are less than 0.5 °C, meeting ASHRAE standards. The model can be used to optimize the parameter settings of CRAC systems under real load conditions, reducing local hotspots in the server room while achieving energy-saving effects.

Authors

Institutions

Publication Details

Journal
Energies
Published
2025-04-03
DOI
https://doi.org/10.3390/en18071803
Citations
2
Primary Topic
Neural Networks and Applications
Type
article
Field-Weighted Citation Impact
4.96

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Prediction of Air-Conditioning Outlet Temperature in Data Centers Based on Graph Neural Networks

Ruping Shao, Yu Wang, Jing Yang, Qilong Sha
2 citations
Energies
Neural Networks and Applications
4.96
article

Prediction of Air-Conditioning Outlet Temperature in Data Centers Based on Graph Neural Networks

Ruping Shao, Yu Wang, Jing Yang, Qilong Sha
article en
2 citations

Abstract

This study addresses the issue of excessive cooling in data center server rooms caused by the sparse deployment of server cabinets. A precise air-conditioning control strategy based on the working temperature response of target cabinets is proposed. CFD software is used to establish the server room model and set control objectives. The simulations reveal that, under the condition of ensuring normal operation and equipment safety in the data center, the supply air temperature of the CRAC (computer room air conditioner) system can be adjusted to provide more flexibility, thereby reducing energy consumption. Based on this strategy, the dynamic load of the server room is simulated to obtain the supply air temperature of the CRAC system, forming a simulation dataset. A graph structure is created based on the distribution characteristics of the servers, and a regression prediction model for the supply air temperature of the CRAC system is trained using graph neural networks. The results show that, in the test set, 95.8% of the predicted supply air temperature errors are less than 0.5 °C, meeting ASHRAE standards. The model can be used to optimize the parameter settings of CRAC systems under real load conditions, reducing local hotspots in the server room while achieving energy-saving effects.

EnergiesVol. 18(7)
Nanjing Tech University (CN)
National Natural Science Foundation of China
Openalex Percentile: Top 6%
Neural Networks and Applications
4.96
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.